Options
Description
Advantages
LD
ILD
LP single-pump
hydraulic module
Single low pressure water pump, water filter,
electronic water flow rate control, pressure
sensors. For more details, refer to the
dedicated chapter (expansion tank not
included; option with built-in hydraulic safety
components)
Quick and easy installation (plug & play)
0602R-1400R 0602R-2000R
LP dual-pump hydraulic
module
Dual low pressure water pump, water filter,
electronic water flow control, pressure
sensors. For more details, refer to the
dedicated chapter (expansion tank not
included; option with built-in hydraulic safety
components)
Quick and easy installation (plug & play)
0602R-1400R 0602R-2000R
HP evap. variable-speed
single-pump
Evaporator hydraulic module equipped with
a high pressure variable-speed pump, drain
valve, air vent and pressure sensors. For
more details, refer to the dedicated section
(expansion tank not included; option with
built-in hydraulic safety components
available.)
Quick and easy installation (plug & play),
significant reduction in pumping energy
consumption level (more than two-thirds),
precise water flow control, improved system
reliability
●
●
Variable-speed dual
high-pressure pump
Dual high pressure water pump with speed
regulator, pressure sensors. Multiple water
flow rate control options. For more details,
refer to the dedicated section.
Quick and easy installation (plug & play),
significant reduction in pumping energy
consumption level (more than two-thirds),
precise water flow control, improved system
reliability
●
●
High nominal energy
efficiency
Higher air flow through the condenser coils
improving heat exchange efficiency on the
condenser
Energy cost reduction and extended
operating envelope (full load operation at
higher air temperature)
●
●
High seasonal energy
efficiency (VSD)
Unit equipped with variable-speed fans
(VSD)
Enhances the unit seasonal energy efficiency
performance and reduces the noise emission
thanks to a smooth fan speed variation.
0602R-1400R
●
High seasonal energy
efficiency (EC)
Variable-speed fans with EC motors
Enhances the unit seasonal energy efficiency
performance and reduces the noise emission
thanks to a smooth fan speed variation.
●
●
High energy efficiency
underfloor heating/
cooling system
application
Optimisation of the refrigerant circuit for the
underfloor heating/cooling system application
Improvement of performances and reduction
of energy costs for the underfloor heating/
cooling system application
No
●
Lon gateway
Two-directional communication board
complying with Lon Talk protocol
Connects the unit by communication bus to a
centralised building management system
●
●
Bacnet over IP
Two-directional high-speed communication
using BACnet protocol over Ethernet network
(IP)
Easy and high-speed connection by Ethernet
line to a BMS. Allows access to multiple unit
parameters
●
●
Energy management
module
EMM Control board with additional inputs/
outputs. See Energy Management Module
section
Extended remote control capabilities (setpoint
reset, ice storage end, demand limits, boiler
on/off command...)
●
●
Contact for refrigerant
leak detection
0-10 V signal to report any refrigerant
leakage in the unit directly (the leak detector
itself must be supplied by the customer)
Immediate customer notification of refrigerant
losses to the atmosphere, allowing timely
corrective actions
●
●
Compliance with Swiss
regulations
Additional tests on the water type heat
exchangers: supply of supplementary test
certifications and certificates (supplementary
documents linked to the Pressure Equipment
Directive)
Compliance with Swiss regulations
●
●
Contact for refrigerant
leak detection
0-10 V signal to report any refrigerant
leakage in the unit directly on the controller
(the leak detector itself must be supplied by
the customer)
Immediate customer notification of refrigerant
losses to the atmosphere, allowing timely
corrective actions
Dec. 2022
Dec. 2022
Compliance with
Russian regulations
EAC certification
Compliance with Russian regulations
●
●
Compliance with
Australian regulations
Unit approved to Australian code
Compliance with Australian regulations
●
●
Coil defrost resistance
heaters
Electric heaters under the coils and the
condensate pans
Prevents frost formation on the coils;
compulsory in heating mode if the outdoor
temperature is below 0°C
No
●
Insulation of the
evaporator inlet/outlet
refrigerant lines
Thermal insulation of the evaporator inlet/
outlet refrigerant lines, with UV-resistant
flexible connection and insulation
Prevents condensation on the evaporator
inlet/outlet refrigerant lines
●
●
12 - OPTIONS
EN-59
AQUACIAT
POWER
™ LD/ILD