Setup
4
ONEAC Sinergy SE II Series UPS User Manual
connection is open, the logic circuit will immediately shut down the UPS output.
• The maintenance bypass switch is intended for use by experienced service personnel only. It is
located at the back of the unit, behind a safety cover (refer to Figure 9). Open the safety cover to
locate and operate the maintenance bypass switch. Instructions for operating the maintenance
bypass switch must be followed or damage to UPS may occur.
Leakage Currents
WARNING: Connect the ground (earth) safety conductor before any other cables are connected.
Batteries
WARNINGS:
• Battery maintenance should only be performed by authorized personnel.
• Batteries installed in the UPS or within the external battery cabinets contain electrolyte. Under
normal conditions the battery cases are dry. A damaged battery may leak electrolyte that can be
dangerous when it is in contact with the skin and cause irritation to the eyes. Should this happen
wash the affected part with copious amounts of water and seek immediate medical attention.
• Voltage is always present on the battery terminals.
• Even when discharged, a battery has the capacity to supply a high short circuit current, which, in
addition to causing damage to the battery itself and to associated cables, may expose the operator to
the risk of burns.
• Batteries should not be kept in storage for periods exceeding 6 months at 77°F (25°C) without being
recharged (having been charged to 100% at the beginning of any such period). If these conditions
are not respected, the performance of the battery can no longer be guaranteed. It is advisable to
recharge the batteries at least once every 4 months.
• Since new batteries often do not provide full capacity after an initial charge it may be necessary to
carry out a number of discharge/recharge cycles before optimum performance is achieved.
• In order to protect the environment, batteries must be disposed of in accordance with the regulations
governing disposal/recycling of toxic and harmful waste.
Repacking of Unit
Do not pack the UPS or external battery cabinets until at least six (6) hours have elapsed since the last
battery recharge.
Place the equipment in bags made of a material sufficiently porous to allow it to breathe [e.g. 4 mil
(100µm) polyethylene].
Do not remove air from the packaging.
When packing unit for movement by common carrier, place on original, or equivalent pallet and repack
in original, or equivalent crate/carton material. See figures 1-4.
Setup
The equipment has been thoroughly checked before shipment. Upon receipt, check the packaging and
ensure that the contents are undamaged. Any damage must be reported to the shipper and any missing
parts must be reported to the supplier immediately.
Unpacking
Care should be taken when removing the packaging in order to avoid damaging the equipment. Check all
packaging materials to ensure that no items are discarded. Remove the packaging following the sequence
illustrated in figures 1-4.
Tools Required
• Hand operated pallet jack
• Scissors
• Screwdriver
ATTENTION: The equipment must be kept upright at all times and handled with care; damage may be
caused if dropped or subjected to severe impact.
Delivery