background image

UPS Start-Up & Shut Down

24

ONEAC Sinergy SE II Series UPS User Manual 

present).

9.   Press the “MENU” button.

10.  Select submenu “Control.”

11.  Press “OK”.

12.  Select submenu “Turn UPS ON/OFF” and press “OK.” The control panel displays “Turn UPS to 

ONLINE.” 

13.  Press “OK” to switch on the inverter. The green “ON” LED is illuminated.

UPS Shutdown 
Procedure

ATTENTION: Carrying out this procedure will interrupt the supply to the connected critical load.

1.   Press the “MENU” button.

2.   Select submenu “Control.”

3.   Press “OK.”

4.   Select submenu “Turn UPS ON/OFF” and press “OK.” The control panel displays “Turn UPS to 

BYPASS.”

5.   Press OK to switch off the inverter.

6.   The display reads: “UPS Bypass Output” and Bypass LED is illuminated.

7.   Open any external switches or circuit breakers downstream of the UPS connecting the load (if present). 

8.   Open both input circuit breakers (Main 1 and Bypass).

9.   Ensure all switches and circuit breakers upstream of the UPS are open.

10.  Ensure that all LEDs on the control panel are extinguished. The UPS is now completely shutdown.

WARNING: Electrical shock hazard: Even when the UPS is disconnected from the mains, hazardous voltages 
may still exist inside the UPS. The UPS receives power from more than one source—AC input and DC input 
from batteries. All input sources (AC and DC) must, therefore, be disconnected before carrying out installation 
or maintenance work inside the UPS.

Maintenance Bypass 
Procedure

1.   Press the “MENU” button.

2.   Select submenu “Control.”

3.   Press “OK.”

4.   Select submenu “Turn UPS ON/OFF.”

5.   Press “OK.” The control panel displays “Turn UPS to BYPASS.”

6.   Press “OK” to switch off the inverter.

7.   The display reads: “UPS Bypass Output” and Bypass LED is illuminated.

8.   Remove the safety cover from the Maintenance Bypass Switch and switch from “UPS” to “Bypass.”

ATTENTION: At this point the critical load is no longer protected by battery backup during interruptions and 
disturbances on the mains supply.

9.   Open both input circuit breakers (Main 1 and Bypass).

10.  The UPS is now switched off, all LEDs are extinguished and the load is supplied directly from the mains 

supply via bypass.

Return from 
Maintenance Bypass 
Procedure

1.   Ensure all switches and circuit breakers upstream of the UPS are closed. 

2.   Close both input circuit breakers (Main 1 and Bypass).

3.   Wait for at least 30 seconds until the output voltage has stabilized (yellow “Bypass” LED illuminated). 

The display reads: “UPS: Bypass.”

4.   Switch the Maintenance bypass switch from “Bypass” to “UPS” and replace the cover.

5.   Press the “MENU” button.

6.   Select submenu “Control.”

7.   Press “OK.”

Содержание SE041XAT

Страница 1: ...please refer to this manual before calling technical services Licenses and Trademarks ONEAC Sinergy ManageUPS and MopUPS are all registered trade marks of ONEAC All other trademarks product and corporate names are the property of their respective owners Entire contents copyright 2008 Chloride All rights reserved Reproduction in whole or in part without permission is prohibited All information subj...

Страница 2: ...epair or return any Chloride product If an Chloride product needs repair or replacement Technical Service issues a Return Material Authorization RMA number along with instructions on how to return the product FCC Compliance ATTENTION Changes or modifications to this unit not expressly approved by the party responsible or in FCC compliance could void the user s authority to operate the equipment Th...

Страница 3: ...t This equipment was tested and complies with the limits for a Class A digital device pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interference when the UPS is operating in a commercial environment The UPS generates uses and can radiate radio frequency energy If installation and use is not in accordance with the instruction manual it m...

Страница 4: ...densation may occur Before you switch on the equipment it must be absolutely dry An acclimatization period of at least two hours is required The equipment must be installed in accordance with the environmental conditions specified in Environmental Conditions on page 7 and Table 2 Installation Data on page 8 Even with all buttons and circuit breakers in the OFF position the UPS is not isolated from...

Страница 5: ...riod If these conditions are not respected the performance of the battery can no longer be guaranteed It is advisable to recharge the batteries at least once every 4 months Since new batteries often do not provide full capacity after an initial charge it may be necessary to carry out a number of discharge recharge cycles before optimum performance is achieved In order to protect the environment ba...

Страница 6: ...Setup ONEAC Sinergy SE II Series UPS User Manual 5 Fig 1 Step 1 Remove Strapping Fig 2 Step 2 Lift Carton Cover 2 1 ...

Страница 7: ...he UPS are two L shaped tie down brackets to prevent the UPS from being moved These brackets are secured to the unit and then to the floor where the UPS will be positioned ATTENTION To ease movement over short distances the UPS is fitted with wheels Before removing the UPS from the pallet raise the leveling feet on the unit ...

Страница 8: ...based on operational temperatures between 68 F and 77 F 20 C and 25 C Operation of the equipment above 77 F 25 C reduces the service life of the batteries dramatically Floor Loading Taking into consideration the weight of the UPS as shown in Appendix A Features and Specifications it is necessary that the floor in the chosen location be capable of supporting the weight of the unit Ventilation and A...

Страница 9: ...nstalled upstream of the equipment Select and configure the isolating device by referring to Table 3 Fuses or Circuit Breakers on page 8 These devices must be designed to work with inductive loads such as transformers Devices should be provided in building installations and other locations The following table indicates the recommended size of input protection devices circuit breakers and fuses tha...

Страница 10: ... switch safety cover 3 Set maintenance bypass switch to Bypass Fig 6 4 Remove terminal area safety cover Fig 6 NOTE If the UPS is fitted with an optional PDU remove cover from PDU In order to gain access to the external electrical connections the rear wiring box protection panel of the UPS must be removed All wiring must be placed in proper conduits and all cabling must be strain relieved per loca...

Страница 11: ...nputs or two separate inputs from same transformer and using same phases for separate Mains and Bypass inputs If the UPS is supplied by a single source connect jumpers from JL1 to BL1 and from JL2 to BL2 Input is connected to Main Line ML1 ML2 terminals See Figure 8 If the bypass input is supplied separately connect bypass line to the Bypass BL1 BL2 terminals Input is connected to Main Line ML1 ML...

Страница 12: ...Fig 9 Rear View Ports for Parallel Operation Maintenance Bypass Switch Input Circuit Breaker for Main Input Input Circuit breaker for Bypass Input Input and Output Terminal Block COM 3 Interface ESD RPO Contacts Slot Interface COM optional Fans External Battery Receptacle ...

Страница 13: ...Line 2 Main 8 22 90 6 22 90 E G Chassis Ground 22 90 22 90 BYPASS BL1 Line 1 Bypass 8 22 90 6 22 90 BL2 Line 2 Bypass 8 22 90 6 22 90 E G Chassis Ground 22 90 22 90 OUTPUT X1 Output Term 1 10 22 90 6 22 90 X2 Output Term 2 10 22 90 6 22 90 X3 Output Term 3 10 22 90 6 22 90 E G Chassis Ground 10 22 90 6 22 90 X4 Output Term 4 10 22 90 6 22 90 X5 Output Term 5 10 22 90 6 22 90 X6 Output Term 6 10 22...

Страница 14: ... X2 X3 are wired together and X5 and X6 are wired together to provide full nameplate rated current at 100 V 50 A for 6 kVA model and 83 A for 10 kVA model However each terminal can supply only 1 2 of the total current and both terminals MUST be connected to the load in order to provide full power Table 5 120 208 240 Output Terminal Voltage Configurations X1 X2 X3 E G X4 X5 X6 Terminal Voltage 120 ...

Страница 15: ...y is not connected To connect an external battery cabinet 1 Insure that the circuit breaker on the back of the external battery cabinet is in the OFF position 2 Using the supplied keyed cable plug one end of cable into the back of the battery closest to the UPS 3 Plug the other end of the keyed cable into the UPS battery sockets 4 Turn the external battery cabinet s circuit breaker to the ON posit...

Страница 16: ...ted supply of energy to the load In practice most mains failures are of relatively short duration Therefore the energy stored in the UPS s batteries is in most cases sufficient to ensure continuous operation of the connected systems until the mains power is reestablished In the event of a long lasting mains failure the UPS can be utilized with shutdown software to enable a controlled shutdown of c...

Страница 17: ...UPS Operation 16 ONEAC Sinergy SE II Series UPS User Manual Fig 12 Block Diagram 120 208 230 240 Volt output Typical for models with I in the part number ...

Страница 18: ...UPS Operation ONEAC Sinergy SE II Series UPS User Manual 17 Fig 13 Block Diagram 100 200 Volt output Typical for models with J in the part number ...

Страница 19: ... screen indicates Status Load Runtime Faults Menu Controls To scroll through the menu controls on the LCD screen press the Menu up or Menu down and Select buttons Each menu has a dedicated number See Figure 15 for menu content Table 8 LED Codes LED LED Code Lighted LEDs ON indicates UPS running online BYPASS indicates load fed from mains via automatic bypass BATT indicates load fed from battery An...

Страница 20: ...Pack 53 Battery Test 54 DC Start 55 UPS Address 56 Series Number 57 Language 58 Logging Menu 6 Event and Time 61 Clear Event Log 62 10 Second Test 34 X Minute Test 34 Test Till Battery Low 34 Cancel Battery Test 34 Test Report 34 Battery Test Time 54 Battery Test Period 54 Manual Auto Test 54 Control Menu 3 Status menu 4 Setup Menu 5 About Menu 7 System Status 1 Start Window 0 See Status Menu tabl...

Страница 21: ... Description O Start Window UPS XX kVA Self testing please wait Wait about 6 seconds Window Description 1 System Status UPS XX kVA UPS UPS Mode Warning Table Fault Table Menu NOTE All UPS Mode Warning Table Fault Table will alternate once a second Window Description 2 Main Menu Control Status Setup Logging About ...

Страница 22: ... Test 342 X Minute Test 343 Test Till Batt Low 344 Cancel Batt Test 345 Battery Test Report No Test In Progress Test In Progress Test OK Test Fail Test Inhibit Test Stop By User Test Autonomy Test Unknown Window Description 4 Status Menu Measured Value Unit L1 Input Volt V Input Frequency 0 1 Hz Output Volt V Output Frequency 0 1 Hz Output Load Output Watt W Output VA VA Battery Volt V Battery Cap...

Страница 23: ...t up 1 1 Internal Batt 0 External Batt20 Batt Total Set up 2 1 Internal Batt 1 External Batt60 Batt Total Set up 3 1 Internal Batt 2 External Batt100 Batt Total Set up 4 0 Internal Batt 1 External Batt40 Batt Total Set up 5 0 Internal Batt 2 External Batt80 Batt Total 54 Battery Test 541 Batt Test Time 1 99 Minutes 542 Batt Test Period 7 180 Days 543 Manual Auto Test Manual Auto 55 DC Start Disabl...

Страница 24: ...attery pack s as necessary The preset language is ENGLISH 8 Close any external switches or circuit breakers downstream of the UPS connecting the load if Table 10 Fault Windows Action Window Details Buzzer alarm 33 The buzzer alarm can be switched ON or OFF Clear fault 32 Present fault condition can be reset if fault condition is cleared either automatically or by the operator technician Get fault ...

Страница 25: ...UPS receives power from more than one source AC input and DC input from batteries All input sources AC and DC must therefore be disconnected before carrying out installation or maintenance work inside the UPS MaintenanceBypass Procedure 1 Press the MENU button 2 Select submenu Control 3 Press OK 4 Select submenu Turn UPS ON OFF 5 Press OK The control panel displays Turn UPS to BYPASS 6 Press OK to...

Страница 26: ...panel to the OFF or down position Note At this time an additional message UTILITY FAILURE will be added to the scrolling display This confirms that the commercial power is off The operator should then go to the LCD panel on the front of the unit and press the MENU Button OK to exit the FAULT MESSAGE display and go to the CONTROL menu Press the MENU OK button again to access the screen that display...

Страница 27: ...hough the UPS is operating in battery mode If the test is successful the BATT LED will extinguish and the UPS will return to On Line mode If the UPS detects a battery malfunction an alarm will be displayed Maintenance Do not use abrasive powder or plastic dissolving solutions to clean the UPS Do not allow liquid to penetrate the interior of the UPS Make sure that the air vents on the UPS are not o...

Страница 28: ...at they be disposed of recycled by an authorized recycling center The manufacturer s service center is fully equipped to deal with such batteries in accordance with the law and with the greatest respect for the environment Contact Technical Support to arrange for maintenance and or battery replacement The typical battery life cycle is 3 to 5 years at an ambient temperature of 77 F 25 C however bat...

Страница 29: ...M The interface slot COM can be fitted with various optional interface cards Optional interface cards include SNMP adapter ManageUPSNET for connecting the UPS to a network Isolated contacts card Installation instructions are included with each card Table 12 RS232 Pins Pin 2 RxD receive RS232 compatible signals Pin 3 TxD transmit RS232 compatible signals Pin 4 not used Pin 7 not used Pin 8 not used...

Страница 30: ...nput or when the mains voltage falls below the lower limit for a minimum of 10 seconds This contact opens approximately 850 ms after the mains have been reestablished The 8 5 contact provides a mirror function opening when the mains voltage fails and closing when main power returns LOW BATT This output provides a N O contact between pins 6 and 5 and an N C contact between pins 7 and 5 The 6 5 cont...

Страница 31: ...sent UPS operation see Control Panel Menus and Displayed Text Options on page 20 ON LED does not illuminate when mains voltage present acoustic alarm active at intervals Input fuse defective or input circuit breaker tripped Replace with fuse of same type or switch on circuit breaker If the problem persists contact technical support FAULT indicator illuminates acoustic alarm active continuously UPS...

Страница 32: ...ns of Warranty This limited warranty does not cover any losses or damage resulting from shipment to or from the customer or from improper installation inappropriate environment abuse modifications adjustments or unauthorized repair For full details of the warranty see ONEAC Warranty Policy and Procedures part number 955 053 Exclusive Remedies Except as set forth herein and except as to title there...

Страница 33: ...ted isolation transformer This provides the highest level of protection from power line disturbances available Two year warranty on power control systems Two year warranty on batteries Hot swappable field replaceable batteries Scalable power and runtimes Integrated manual and automatic bypass Comprehensive front panel control indicators Remote Power Off RPO ESD Operates as a frequency converter Fe...

Страница 34: ...W optional power cord HW Output connection HW attached PDU optional HW attached PDU optional Internal battery 20 VRLA 12V 20 VRLA 12V Battery type sealed maintenance free lead acid VRLA Battery test Automatic user selectable Battery recharge time to 90 available capacity 5 8 hours internal batteries Battery management Automatic runtime adjustment protection against deep discharge UPS dimensions Hx...

Страница 35: ...pecifications UPS Model SE041 SE061 SE081 SE101 Table 15 SE II Series UPS Typical UPS Runtimes Model Number Internal Battery Internal Battery Plus 1 Ext Battery Per Power Head Internal Battery Plus 2 Ext Battery Per Power Head SE041 half load full load min 37 15 156 66 310 130 SE061 half load full load min 21 9 84 39 175 78 SE081 half load full load min 21 6 73 23 140 45 SE101 half load full load ...

Страница 36: ...gs of all parallel units The table on page 22 shows setup parameters setup menu 5 The settings of output voltage must be the same General information for designing a parallel system UPSs configured as a parallel system must all be configured for single input same source to both main and bypass mode Jumpers must be installed between JL1 BL1 and between JL2 and BL2 on each unit When connecting mains...

Страница 37: ...Appendix B Paralleling UPS Devices 36 ONEAC Sinergy SE II Series UPS User Manual Fig 19 Paralleling Sinergy models with A in the part numbers ...

Страница 38: ...Appendix B Paralleling UPS Devices ONEAC Sinergy SE II Series UPS User Manual 37 Fig 20 Paralleling Sinergy models with I in the part number ...

Страница 39: ...e switched to OFF on all UPSs All terminals breakers and plugs of UPS can be found on the respective rear panels of UPS batteries Step B 1 Remove jumper from parallel terminals S1 S2 from each of the UPSs blocks to be connected 2 Connect the input terminals per the Connecting Power Cables on page 10 from each of the UPSs terminal blocks to the mains distribution 3 Connect the output terminals per ...

Страница 40: ...e will allow for full rated output of the parallel system UPS will have the BYPASS LED illuminated 7 Press the MENU button on UPS 1 8 Select submenu CONTROL 9 Press OK the LCD displays TURN UPS TO ONLINE 10 Press OK the UPS system will stay waiting in BYPASS mode 11 Repeat step 7 10 on UPS 2 and UPS 3 NOTE After a few seconds the BYPASS LEDs on UPSs will extinguish and all ON LED s will illuminate...

Страница 41: ...er Manual SE202 20 60 18 SE202XAT 2 SE202XIT 2 SE202XJT 2 2 SE101 2 SEBP610 2 SE202 20 117 35 SE202XAT 4 SE202XIT 4 SE202XJT 4 2 SE101 4 SEBP610 2 Table 16 Sinergy Parallel Kits and Runtimes Sinergy Parallel KIt Model No kVA Runtime half load full load Part No Kit Includes ...

Страница 42: ...Appendix B Paralleling UPS Devices ONEAC Sinergy SE II Series UPS User Manual 41 ...

Отзывы: