![CHINSC ELECTRIC SVF-G7 Series Скачать руководство пользователя страница 189](http://html.mh-extra.com/html/chinsc-electric/svf-g7-series/svf-g7-series_operation-manual_2602262189.webp)
SVF-G7 Series Frequency Inverter Operation Manual
Chapter 8 Troubleshooting
184
Fault
code
Fault
categories
Possible
reasons
of
fault
Actions
E010
DC
Bus
under-voltag
e
Low
AC
supply
voltage
Check the AC supply
voltage
E011
Motor
over-load
Low
AC
supply
voltage
Check the AC supply
voltage
Improper motor’s rated
current
Modify motor’s rated
current
Load
in
creases
suddenly
Check the load, adjust
the value of torque
boost
The drive's and motor's
powers don't match
Use suitable motor
E012
Drive
over-load
Too short Acc time
Prolong the Acc time
The
rotating
motor
re-start
Avoid
re-start
after
the
drive
stops
instantly
Low
AC
supply
voltage
Check the AC supply
voltage
Too heavy load
Select a high power
drive
E013
Input
phase
loss
Any of phase R, S and
T cannot be detected
Check
the
input
power supply
Check
the
drive’s
output wiring
Содержание SVF-G7 Series