![CHINSC ELECTRIC SVF-G7 Series Скачать руководство пользователя страница 187](http://html.mh-extra.com/html/chinsc-electric/svf-g7-series/svf-g7-series_operation-manual_2602262187.webp)
SVF-G7 Series Frequency Inverter Operation Manual
Chapter 8 Troubleshooting
182
Chapter
Chapter
Chapter
Chapter 8
8
8
8 Troubleshooting
Troubleshooting
Troubleshooting
Troubleshooting
Table 8-1 listed the possible faults of SVF-G7, and the fault code indicate
range is from E001 and E004 ~ E025. Once a fault occurs, you may check it
against the table and record detailed phenomena before seeking service from
your supplier.
8.1 Faults and actions
Table 8-1 Faults and actions
Fault
code
Fault
categories
Possible
reasons
of
fault
Actions
E001
IGBT
module’s
shorted
Too short Acc time
Prolong the Acc time
Inside
IGBT
is
damaged
Seek service
Interference causes the
malfunction
Check
peripheral
equipment
whether
has
strong
interference
Grounded is not good
Seeking service
E004
Over-current
during
acceleration
Too short Acc time
Prolong the Acc time
Low
AC
supply
voltage
Check
the
input
power supply
Drive
power
is
too
small
Select a high power
drive
E005
Over-current
during
deceleration
Too short Dec time
Prolong the Dec time
Low
AC
supply
voltage
Use suitable dynamic
braking kit