EM11 User’s Manual
Appendix II
157
Code
Parameter Name
Setting range
Default
Property
b7-21
VDO valid state
selection
Unit's digit: VDO1.
0: Positive logic valid
1: Reverse logic valid
Ten's digit: VDO2
0, 1 (same as unit's digit)
Hundred's digit: VDO3.
0, 1 (same as unit's digit)
Thousand's digit: VDO4.
0, 1 (same as unit's digit)
Ten thousand's digit: VDO5.
0, 1 (same as unit's digit)
00000
☆
Group b8: AI/AO Correction
b8-00
Ideal voltage of AI1
calibration 1
0.500~4.000 V
2.000V
☆
b8-01
Sampling voltage of
AI1 calibration 1
0.500~4.000 V
2.000V
☆
b8-02
Ideal voltage of AI1
calibration 2
6.000~9.999 V
8.000V
☆
b8-03
Sampling voltage of
AI1 calibration 2
6.000~9.999 V
8.000V
☆
b8-04
Ideal voltage of AI2
calibration 1
0.500~4.000 V
2.000V
☆
b8-05
Sampling voltage of
AI2 calibration 1
0.500~4.000 V
2.000V
☆
b8-06
Ideal voltage of AI2
calibration 2
6.000~9.999 V
8.000V
☆
b8-07
Sampling voltage of
AI2 calibration 2
6.000~9.999 V
8.000V
☆
b8-08
Ideal voltage of AI3
calibration 1
0.500~4.000 V
2.000V
☆
b8-09
Sampling voltage of
AI3 calibration 1
0.500~4.000 V
2.000V
☆
b8-10
Ideal voltage of AI3
calibration 2
6.000~9.999 V
8.000V
☆
b8-11
Sampling voltage of
AI3 calibration 2
6.000~9.999 V
8.000V
☆
b8-12
Ideal voltage of AO1
calibration 1
0.500~4.000 V
2.000V
☆
b8-13
Measured voltage of
AO1 calibration 1
0.500~4.000 V
2.000V
☆
b8-14
Ideal voltage of AO1
calibration 2
6.000~9.999 V
8.000V
☆
b8-15
Measured voltage of
AO1calibration 2
6.000~9.999 V
8.000V
☆
b8-16
Ideal voltage of AO2
calibration 1
0.500~4.000 V
2.000V
☆
Appendix II
EM11 User’s Manual
158
Code
Parameter Name
Setting range
Default
Property
b8-17
Measured voltage of
AO2 calibration 1
0.500~4.000 V
2.000V
☆
b8-18
Ideal voltage of AO2
calibration 2
6.000~9.999 V
8.000V
☆
b8-19
Measured voltage of
AO2 calibration 2
6.000~9.999 V
8.000V
☆
Group b9: Keypad and Display
b9-00
STOP/RESET key
function
0: STOP/RESET key enabled only in
operation panel control
1: STOP/RESET key enabled in any
operation mode
0
☆
b9-01
MF.K Key function
selection
0: MF.K key disabled
1: Switchover between operation panel
control and remote command control
(terminal or communication)
2: Switchover between forward rotation and
reverse rotation
3: Forward JOG
4: Reverse JOG
0
☆
b9-02
LED display running
parameters 1
0000~FFFF
Bit00: Running frequency 1 (Hz)
Bit01: Set frequency (Hz)
Bit02: DC Bus voltage (V)
Bit03: Output voltage (V)
Bit04: Output current (A)
Bit05: Output power (kW)
Bit06: Output torque (%)
Bit07: DI input status
Bit08: DO output status
Bit09: AI1 voltage (V)
Bit10: AI2 voltage (V)
Bit11: AI3 voltage (V)
Bit12: Count value
Bit13: Length value
Bit14: Load speed display
Bit15: PID setting
0x1f
☆