Chiltrix Inc.
www.Chiltrix.com
47
F9
Exhausted gas temp.
sensor fault
Flash’s
7
times
1.
Reconnect the sensor.
2.
Measure the sensor
resistance at different
temperatures, if it is
out of range, change
the sensor.
FA
Outdoor module
overheat, over-current
Flash’s
5
times
IPM temperature too high,
compressor current too
high.
1. Disconnect the power
supply and reconnect it
after 3 minutes.
2. Check if the IPM
connection wires are not
loose or IPM is burned.
P1 high
pressure
protection
Flash’s
2 times
1.
High pressure
switch loose or
faulty.
2.
There is air
inside the water
circuit.
3.
Water flow
volume is too
low, water
pump is too
small or faulty.
4.
Throttling
device
(expansion
valve) problem.
5.
There is air
inside the
refrigerant
system or
refrigerant
volume is too
high.
1.
If the error displays before the
compressor starts, it means high pressure
switch error. Please reconnect high
pressure switch or change the switch. If
the error displays when water temp is
about 104°F, please check if the high
pressure switch or mid pressure switch is
misconnected by mistake. Refer to the
wiring diagram.
2.
Clean and purge the air from the water
circuit.
3.
Clean the Water circuit filter or add a
bigger water pump if water flow is not
enough.
4.
Open the thermostatic expansion valve
360~180°,
5.
Measure the refrigerant pressure, re-
vacuum the system and recharge the
refrigerant.
Содержание AC series Heating & Cooling series CX30
Страница 4: ...Chiltrix Inc www Chiltrix com 4 Components ...
Страница 10: ...Chiltrix Inc www Chiltrix com 10 Freeze protection ...
Страница 15: ...Chiltrix Inc www Chiltrix com 15 Clearances unit mm 200mm 8 350mm 14 400 16 500 20 1000 40 ...
Страница 24: ...Chiltrix Inc www Chiltrix com 24 G1 Valve Wiring and Parameters ...
Страница 27: ...Chiltrix Inc www Chiltrix com 27 G3 VALVE Seasonal Switch Valve Solar Preheat Valve ...