Chiltrix Inc.
www.Chiltrix.com
26
G3 Valve: Seasonal Switch Valve or Solar Preheat Valve
The G3 port can be used to control a seasonal switch valve. The seasonal switch valve is used to isolate the
floor coils from the fan coils when switching over from heating to cooling. The seasonal switch valve is
controlled by parameter 14. When parameter 14 is 0, the valve is configured as a seasonal Switch.
When parameter 14 is 1, the valve is configured as a solar pre-heat valve. The CX30 compares the solar
tank temp and AC returned temp. When the solar tank temp – AC returned temp is ≥ 5
℃
, the 3-way valve
G3 will be on; when solar water tank temperature minus the air conditioning returned temperature is less
than 2°C, G3 will be off.
Содержание AC series Heating & Cooling series CX30
Страница 4: ...Chiltrix Inc www Chiltrix com 4 Components ...
Страница 10: ...Chiltrix Inc www Chiltrix com 10 Freeze protection ...
Страница 15: ...Chiltrix Inc www Chiltrix com 15 Clearances unit mm 200mm 8 350mm 14 400 16 500 20 1000 40 ...
Страница 24: ...Chiltrix Inc www Chiltrix com 24 G1 Valve Wiring and Parameters ...
Страница 27: ...Chiltrix Inc www Chiltrix com 27 G3 VALVE Seasonal Switch Valve Solar Preheat Valve ...