INITIAL TEMPERATURE SETTINGS
*Note – Cooling set points refer to the CX30 outlet temperature, however, the system is managed by a 9°F ΔT
controller and is measured in C (5°C). Default setting for cooling should be 12°C, therefore the controller returned
temp would be set to 17°C. This will create a 54°F leaving water temperature which is the correct setting. The
same applies to the heating setting. The default setting for heating should be 40°C, therefore the returned temp
would be set to 35°C, this will create a 95°F leaving water temperature which is the correct setting.
Detailed settings as follows:
N0. Meaning
Selected
temperature range
Recommended controller
temperature setting
Operation for
modifying settings
1
AC cooling
returned
water temp
10°C ~ 25°C
12-17°C
2
AC heating
returned
water temp
10°C ~ 55°C
35-40°C
3
DHW temp
10°C ~ 50°C
50°C
UNIT OPERATION
Time adjustment
Press the
key, time “hour” value will flash, then press
or
, the value will increase
or decrease. Press and hold either key and the value will cause a continuous increase or
decrease. Press the
to confirm settings and exit the time mode.
5.
Timer setting
You can set one time to start and one time to turn off. You can select cycling the on /off settings or
just turn on and follow the set point.
A.
Setting the time “on” method:
1.
Press
for 3 seconds to set the time, you will see
flash as show below.
Содержание AC series Heating & Cooling series CX30
Страница 4: ...Chiltrix Inc www Chiltrix com 4 Components ...
Страница 10: ...Chiltrix Inc www Chiltrix com 10 Freeze protection ...
Страница 15: ...Chiltrix Inc www Chiltrix com 15 Clearances unit mm 200mm 8 350mm 14 400 16 500 20 1000 40 ...
Страница 24: ...Chiltrix Inc www Chiltrix com 24 G1 Valve Wiring and Parameters ...
Страница 27: ...Chiltrix Inc www Chiltrix com 27 G3 VALVE Seasonal Switch Valve Solar Preheat Valve ...