Chiltrix Inc.
www.Chiltrix.com
14
Heat Pump Installation
Installation position
Note:
Installation must be carried out by professional personnel
.
1.
The recommended mounting pad should be 1” to 1 ½” above ground level.
2.
A drainage path or other facilities should be arranged around the outdoor unit to avoid
flooding the outdoor unit.
3.
To install the unit on a balcony or on top of a building, the installation site must meet the
allowable bearing capacity of the building structure without affecting the structural safety.
4.
Ensure the unit is well ventilated; the direction of air exhaust should be kept away from the
windows of neighboring buildings. Adequate service clearance should be kept around the unit.
5.
The unit should not be installed in places accompanied with oil, inflammable gases; corrosive
components e.g. sulfur compound, or high-frequency equipment.
6.
The unit must be installed upon a reliable machine base or framework. Weight capacity of
framework should be 3 times of the outdoor unit’s body weight, and safeguard measures should be
taken to avoid a malfunction of the fasteners.
7.
The unit must have extra precautions taken when it is installed at sites with hurricane/ earthquake
hazards. Consult the appropriate professional to determine the needed requirements
8.
Midair or suspended installation should be avoided as much as possible, falling machines may result
in personal injury and property damage.
Содержание AC series Heating & Cooling series CX30
Страница 4: ...Chiltrix Inc www Chiltrix com 4 Components ...
Страница 10: ...Chiltrix Inc www Chiltrix com 10 Freeze protection ...
Страница 15: ...Chiltrix Inc www Chiltrix com 15 Clearances unit mm 200mm 8 350mm 14 400 16 500 20 1000 40 ...
Страница 24: ...Chiltrix Inc www Chiltrix com 24 G1 Valve Wiring and Parameters ...
Страница 27: ...Chiltrix Inc www Chiltrix com 27 G3 VALVE Seasonal Switch Valve Solar Preheat Valve ...