Chiltrix Inc.
www.Chiltrix.com
46
F2
Rating module PFC
error
Flash
IPM module (PFC)
connection wire loose or
IPM module defective.
1.
Check if there is any burn
marks on IPM PCB.
F3
Compressor stopped
abnormally
Flash
Power supply error,
electromagnetic
interference, Outdoor PCB
error or bad compressor.
1. Shut off the power supply
wait for 3 minutes then
reconnect the power.
2. Check that all wire
connections are not loose.
F4
Outdoor IPM
module radiator
sensor fault
Flash’s 5
times
IPM module temp sensor
error.
Reconnect or change the
sensor.
F5
Outdoor unit current
sensor fault
Flash’s 8
times
Running Current sensor
fault or loose wires.
Reconnect or change the
sensor.
F6
IPM or module
control board fault
Flash’s
14 times
1.
Communication wire
between IPM module
and outdoor PCB.
2.
IPM Module is burned
or IPM has no power
from the AC contactor.
3.
Outdoor PCB
Communication port
error.
4.
Check if the IPM
module (PFC)
connection wire with
outdoor PCB is not
loose.
5.
Check if there is any
burn marks on IPM.
6.
Check the AC
connection at the IPM.
7.
Check if the outdoor
PCB has an error.
F7
Compressor fail to
start
Flash
Decided by Outdoor unit
Check the wire
connections, Refrigeration
PCB and compressor.
F8
Outdoor unit
overcurrent
Flash’s
11
times
Compressor working
current too high
1. Check the compressor
wire connections.
2. Disconnect the power
supply and reconnect it
after 3 minutes.
3. Check if the refrigerant
volume is correct
4. Open the heat
expansion valve
360~180°
Содержание AC series Heating & Cooling series CX30
Страница 4: ...Chiltrix Inc www Chiltrix com 4 Components ...
Страница 10: ...Chiltrix Inc www Chiltrix com 10 Freeze protection ...
Страница 15: ...Chiltrix Inc www Chiltrix com 15 Clearances unit mm 200mm 8 350mm 14 400 16 500 20 1000 40 ...
Страница 24: ...Chiltrix Inc www Chiltrix com 24 G1 Valve Wiring and Parameters ...
Страница 27: ...Chiltrix Inc www Chiltrix com 27 G3 VALVE Seasonal Switch Valve Solar Preheat Valve ...