Make sure the floor can take the weight of the stove, the flue, the hearth and any
decorative surround.
3.e
Floors
A hearth is made up of 2 layers: a constructional hearth (base concrete layer) and a
superimposed hearth (top decorative layer). In some circumstances a superimposed
hearth is acceptable on its own. All of our stoves require a constructional hearth
unless
the stoves are
either
on a plinth
or
have a base heat shield fitted.
3.d
Hearth
All models without
base heat shield or plinth
Constructional total depth (incl.
superimposed) 125mm
All models on plinth
Superimposed 12mm (minimum)
All models with base heat shield
Superimposed 12mm (minimum)
In front of the stove
225mm (minimum)
Both sides of the stove
150mm (minimum)
NB. Do not place any soft furnishings within 1150mm of the stove
150mm
Minimum distance from stove to edge of superimposed hearth
225mm
150mm
All freestanding stoves require a superimposed hearth of at least 850x850mm square
(in addition to any constructional hearth requirements)