Chapter
5Maintenance and Checkup
CMN023-005
原本
(original instructions)
59
E
nglis
h
Troubleshooting
No.
Trouble phenomenon
Cause
Remedy
①
Organic EL display
shows nothing.
Power not turned on.
Turn on the power.
Blown fuse
Replace the fuse.
Replacing Fuse” (page 55)
②
Motor fails to start or
suddenly stops
running.
Faulty motor
Call for repair.
The motor must be replaced.
Stopped due to
overload or abnormal
temperature
[1] Check that the exhaust/suction ports are
not blocked.
[2] Check the rated voltage.
[3] Check for multiple connections.
[4] Check for motor overheat due to either
filter clogging or suction temperature.
After the checks [1] to [4], take corrective
action, and then turn the main power switch
off and back on.
If the operation cannot resume, the
temperature thermostat of the motor may
be active. Turn off the main power, and
after 30 minutes, resume the operation.
Primary or secondary
filters not in place
Install the primary and secondary filters
correctly.
Each snap lock is
unfastened
Engage the snap locks case securely.
③
Lower suction force
Clogged filter
Replace filter.
If filters are left clogged, the device may
result in “untrapped particles” or
“temperature rise in dust collector”.
Clogged piping or
suction port
Check if piping is clogged or the suction port
blocked.
Faulty motor
Call for repair.
The motor must be replaced.
④
Untrapped particles
Improper filter
installation
Reinstall filters.
(
Page 53
)
Filter broken or past
service life
Replace filters.
(
Page 53
)
Clogged filter
Replace filters.
Replacing Filters” (Page 53)
⑤
Odd noise or vibration
from motor
Foreign matter
entered in blower.
Call for repair.
Broken motor bearing Call for repair.
Note: For other phenomena, contact CHIKO AIRTEC.
Содержание CBA-1500AT3-HC-DSA-V1
Страница 5: ...1 CMN023 005 Translation of the original instructions 3 1 1 1 1 2 10 60 80 1 3 0 40 80 100 1 000...
Страница 6: ...1 4 1 4 2 OFF 1 5...
Страница 7: ...1 CMN023 005 Translation of the original instructions 5 1 6...
Страница 8: ...2 6 2 2 1 200V 220 230V CE 1 1 2 1 1 HEPA 1 3m 200V 1 220 230V CE 1 1...
Страница 10: ...2 8 2 3 AT3 EL OLED No 1 7 2 4 9 4 15 1 1 1 1 OFF 3 3 3 14 ON ENTER 3 3 3 14 4 15 MODE SELECT 4 15...
Страница 12: ...2 10 2 4 3 OP kPa SP kPa DP kPa EP kPa Blower Runtime h 18 Total h Moter...
Страница 13: ...3 CMN023 005 Translation of the original instructions 11 3 3 1 3 1 1 0 40 80 RH REMOVE 1 1 1...
Страница 14: ...3 12 1 2 2 3 4 OFF ON 1 A OFF 40 50 A 2...
Страница 22: ...5 20 5 5 1 WARN2 1 5 1 1 1 1 1 2 2 1 3 1 4 2 1...
Страница 24: ...5 22 3 ACC 4 5 6 5 2 1 Littell fuse 218 250V 15A 1 2 3 ACC...
Страница 25: ...5 CMN023 005 Translation of the original instructions 23 5 3 CR2477 CR2477 1 2 3 2 4 5 6 7 5 4 1 1 1 1 5 5...
Страница 28: ...5 26 5 7 EL ON ON 5 2 22 1 2 3 4 1 4 ON OFF 30 1 2 1 2 5 1 20 5 1 20 5 1 20 5 1 20...
Страница 29: ...6 CMN023 005 Translation of the original instructions 27 6 6 1 6 1 1...
Страница 30: ...6 28 1 5V 0 2V LOW DC 1 2...
Страница 34: ...7 32 7 3 7 3 1 CBA 1500AT3 HC DSA V1...
Страница 35: ...CMN023 005 Translation of the original instructions 33 12 7 2 7 2 31...
Страница 36: ...34...
Страница 67: ...Chapter 7Appendix CMN023 005 original instructions 65 English Electrical Diagram 7 3 1 CBA 1500AT3 HC DSA V1...
Страница 69: ...MEMO...