Chapter
4Configuring Settings
【
MODE SELECT mode
】
CMN023-005
原本
(original instructions)
51
E
nglis
h
Air Volume-Down Alert Timing Setting Mode
This mode allows for changing the timing for displaying an air volume-down warning (WARN4) as desired.
1.
Move to the MODE SELECT mode.
2.
Press the Up/Down arrow buttons to move to the air volume-down alert timing setting mode
(“Volume Down ST”).
3.
Press the ENTER button.
The current setting appears.
The default is 50%, displayed as “3: Down to 50%”.
4.
Press the Up/Down arrow buttons to select a timing between 30 to 70%.
A lower setting causes the air volume-down alert to occur later, and vice versa.
5.
Press the ENTER button to determine the setting.
6.
To exit this mode, press the MODE SELECT button to return to normal mode.
Other Setting Mode
The parameters listed below can be set.
•
Date/time setting
Clock Calibration Mode(Page 51
)
”
•
Accumulated run time resetting
Accumulated Run Time Reset Mode(Page 52
)
•
Setpoint resetting
4.5.1
Clock Calibration Mode
This mode sets date and time.
1.
Move to the MODE SELECT mode.
2.
Press the Up/Down arrow buttons to move to the other setting mode (“Other Setting”).
3.
Press the ENTER button.
The screen displays “Time Adjust”.
4.
Press the ENTER button.
The date setting screen appears.
5.
Press the Up/Down arrow buttons to change the value.
6.
Press the ENTER button to determine the value.
Set the value in this order: year, month, and day.
7.
After the date is set, the time setting screen appears.
100% of filter performance is available.
The initially registered value is taken as
100%.
Note: The initial pressure applies when the
suction hose and hood are set in
place.
Differential
pressure lower
Less than 30% of
filter performance
is available.
Filter performance
Setpoint
To advance the lamp-lighting timing To delay the lamp-lighting timing
Содержание CBA-1500AT3-HC-DSA-V1
Страница 5: ...1 CMN023 005 Translation of the original instructions 3 1 1 1 1 2 10 60 80 1 3 0 40 80 100 1 000...
Страница 6: ...1 4 1 4 2 OFF 1 5...
Страница 7: ...1 CMN023 005 Translation of the original instructions 5 1 6...
Страница 8: ...2 6 2 2 1 200V 220 230V CE 1 1 2 1 1 HEPA 1 3m 200V 1 220 230V CE 1 1...
Страница 10: ...2 8 2 3 AT3 EL OLED No 1 7 2 4 9 4 15 1 1 1 1 OFF 3 3 3 14 ON ENTER 3 3 3 14 4 15 MODE SELECT 4 15...
Страница 12: ...2 10 2 4 3 OP kPa SP kPa DP kPa EP kPa Blower Runtime h 18 Total h Moter...
Страница 13: ...3 CMN023 005 Translation of the original instructions 11 3 3 1 3 1 1 0 40 80 RH REMOVE 1 1 1...
Страница 14: ...3 12 1 2 2 3 4 OFF ON 1 A OFF 40 50 A 2...
Страница 22: ...5 20 5 5 1 WARN2 1 5 1 1 1 1 1 2 2 1 3 1 4 2 1...
Страница 24: ...5 22 3 ACC 4 5 6 5 2 1 Littell fuse 218 250V 15A 1 2 3 ACC...
Страница 25: ...5 CMN023 005 Translation of the original instructions 23 5 3 CR2477 CR2477 1 2 3 2 4 5 6 7 5 4 1 1 1 1 5 5...
Страница 28: ...5 26 5 7 EL ON ON 5 2 22 1 2 3 4 1 4 ON OFF 30 1 2 1 2 5 1 20 5 1 20 5 1 20 5 1 20...
Страница 29: ...6 CMN023 005 Translation of the original instructions 27 6 6 1 6 1 1...
Страница 30: ...6 28 1 5V 0 2V LOW DC 1 2...
Страница 34: ...7 32 7 3 7 3 1 CBA 1500AT3 HC DSA V1...
Страница 35: ...CMN023 005 Translation of the original instructions 33 12 7 2 7 2 31...
Страница 36: ...34...
Страница 67: ...Chapter 7Appendix CMN023 005 original instructions 65 English Electrical Diagram 7 3 1 CBA 1500AT3 HC DSA V1...
Страница 69: ...MEMO...