2.0 C-Linx PROGRAMMING OPTIONS
Cheetah Xi Programming Manual
2-3
P/N: 06-651
Rev 1, 09/2013
Exhibit 2-2: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Time
Functions
Alarm Sensitivity Changes
Daytime Sensitivities start/stop
Y
12:00 AM – 12:00 AM
Days that use daytime sensitivity Y Sunday
–
Saturday
Use Daylight Savings Time
Y
Enabled
/ Disabled
Holiday Schedule
Night time sensitivity
Y
20 days total (mm/dd/yyyy)
3
DACT Auto Test
DACT Auto test start hour
Y
0 – 23
(2 default)
DACT Auto test period (hrs.)
Y
0
- 24
NAC
P10 and P11 (NAC 1 & NAC 2)
Sync Protocol
Y
NO
/ Gentex / System
Sensor / Wheelock
1,2
State (Activation)
Y
Alarm
/ Pre-Alarm 1 / Pre-
Alarm 2 / Supervisory /
Trouble / Process / Release /
Pre-discharge
Silenceable Y
Silenceable
/ Non
silenceable
Zone Assignment
Y
1 –
254
Circuit Y
Enabled
/ Disabled
Drill Y
Enabled
/
Disabled
Walktest Y
Enabled
/
Disabled
Non-Silence for Waterflow
Activation
Y
Enabled /
Disabled
Panel Sync Protocol
Y
Gentex
/ System Sensor /
Wheelock
Relays
P2 Main Board Relay
Relay Selection
Y
R1
/ R2
4
State (Activation)
Y
Alarm
/ Pre-Alarm 1 / Pre-
Alarm 2 / Supervisory /
Trouble / Process / Zone
Disable / Release / Pre-
discharge / Abort
Silenceable Y
Non-Silenceable
/
Silenceable
Relay Y
Enabled
/ Disabled
Zone Assignment
Y
1 –
254
Drill Y
Enabled
/
Disabled
Notes:
1.
If synchronization is selected, both NAC circuits will use the same sync protocol.
2.
Refer to Fike document 06-186 for compatible notification appliances.
3.
Only allows the installer to assign the night time sensitivity to a different obscuration level than during normal working hours.
No other functions are effected or disabled
4.
Allows on board relays to be configured from the default setting of Alarm for R1 and Supervisory for R2 to the states listed in
State (Activation)