2.0 C-Linx PROGRAMMING OPTIONS
2-14
Cheetah Xi Programming Manual
Rev 1, 09/2013
P/N: 06-651
Exhibit 2-13: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Defaults
(Mini Monitor
Module)
Loop Number of Device
Y
1 -
4
1
Address of Device
Y
1
– 254
Custom Message
Y
60 character user defined
(1-001 MINI MANALRM
Loop 1 - Address 001)
Custom Message
Y
Default /
User Defined
Zone Assignments
Y
1
– 254
2
Predischarge Type
Y
Alarm Device Only
/ 1
st
Cross Zone Device / 2
nd
Cross Zone Device / Count
Zone Device / Single Release
Device
6
Alarm Verification
Y
Time: 0 – 60 seconds
Y
Enabled
/ Disabled
Input Function Type
Y
No Input Function
/
ManAlarm / Detection/
Waterflow /Pre-Alarm 1 / Pre-
Alarm 2 / Supervisory /
Trouble / Process / PAS
Inhibit / Reset / Silence /
Acknowledge / Drill / Zone
Disable / Fan Restart /
Smoke Control Confirmation /
Manual Alarm Stage 2 / AHU
Fire Dept Key /Manual
Release / Manual Release
with Countdown / Abort /
Watermist Activation
Y
Verify Time: 0 – 255 seconds
3
Y
Latching
/ Non-Latching
4
Y
Normally Open
/ Normally
Closed
5
Y
No Short Detection
/ Short
Detection
Notes:
1.
Cheetah Xi can have up to four (4) addressable loops.
2.
Can be assigned to 4 discrete zones, 2 zone ranges or 1 range and 2 discrete zones.
3.
If monitor module function type is set to Detection, an alarm verification time can be set.
4.
Either = Waterflow, PA1, PA2, Supervisory, Trouble, Process, PAS Inhibit; Non-Latch = Silence, Acknowledge, Drill, Zone
Disable, Fan Restart, Smoke Confirmation, Abort; Latching = ManAlarm, Detection, Reset, Manual Alarm Stage 2, Manual
Release, Manual Release with Countdown, Watermist.
5.
NO Contacts = Detection, Manual Alarm, Reset, Manual Alarm Stage 2, Manual Release, Manual Release with Countdown,
Abort, Watermist; NO/NC Contacts = Waterflow, PA1, PA2, Supervisory, Trouble, Process, PAS Inhibit, Silence, Acknowledge,
Drill, Zone Disable, Fan Restart, Smoke Confirmation.
6.
If monitor module function type is set to Detection, a Predischarge Type must be set.