4.0 CONFIGURATION MENU
Cheetah Xi Programming Manual
4-11
P/N: 06-651
Rev 1, 09/2013
4.2.1.2
HOW TO CHANGE A DEVICES RELEASE FEATURES
Sensors and input modules connected to the signaling line circuit (SLC) can be assigned a pre-discharge type
and countdown type variable, each of which affects how the Cheetah Xi system responds when the device
goes into alarm. Both variables are stored in both panel memory and device memory. When the panel
“LEARN” function is initiated, the variables will be uploaded from the SLC device into panel memory.
Likewise, configuring a device from this configuration screen writes the variables into the device.
From the “Device Configuration Menu” screen, press the F2 key to display the “Release Features” screen, as
shown below:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
L - A D R : D E V I C E
T Y P E
B
P R E - D I S C H
T Y P E :
A
C
C O U N T D O W N :
A U T O M A T I C
D
Exhibit 4-15: Release Features Screen
•
Row A (L-ADR) - Allows you to select the loop and address of a specific SLC device in order to
display its configuration parameters. Type of device configured at the selected address will be
display. Use the
◄►
arrow keys to position the cursor under any of the fields; then use the +/- keys
to change to a different loop or address number.
•
Row B – Allows you to select the pre-discharge type (A – F) for the selected device as described
below. Use the
◄►
arrow keys to position the cursor under the field; then use the +/- keys to
change the field value.
¾
A = Alarm Only
. No pre-discharge in a zone will occur from the alarm of this device.
¾
B = Cross Zone “B”.
Pre-discharge will occur in the zones assigned to this device when
a corresponding “C” type is alarmed.
¾
C = Cross Zone “C”.
Pre-discharge will occur in the zones assigned to this device when
a corresponding “B” type is alarmed.
¾
D = Counting Zone.
Pre-discharge will occur when two or more “D” types are alarmed in
the assigned zones.
¾
E = Single Pre-discharge.
Only one alarmed “E” type will cause pre-discharge in the
assigned zones.
¾
F = Single Release.
This type skips pre-discharge and causes immediate release in the
assigned zones.
After changing the pre-discharge type, a “*” character will appear to the right of the type variable
field. You must press the ENTER switch to store the variable change in device memory.
•
Row C – Allows you to select whether the selected device will utilize the Automatic or Manual
countdown timer set for the zone should it cause a pre-discharge in any of its assigned zones. Use
the
◄►
arrow keys to position the cursor under the fields; then use the +/- keys to change the field
value. Certain devices must be assigned a pre-discharge type first before this value can be
changed.
¾
Automatic Countdown Devices
= Photo, Heat, Photo/Heat, Photo Duct, and Ion
detectors.
¾
Manual Countdown Devices
= Pull Station, Monitor Module, and Mini Monitor Modules.