![Check Point 61000 Скачать руководство пользователя страница 49](http://html.mh-extra.com/html/check-point/61000/61000_getting-started-manual_2594915049.webp)
Step 3: Installing Hardware Components and Connecting Power Cables
Check Point 61000 Security System Getting Started Guide R75.40VS for 61000 | 49
6.
Connect the Return cables to the battery:
a)
Using the crimping tool, connect two 6 AWG wire leads to two lugs.
b)
Attach the two wired lugs to the
Return
terminal studs on the PEM. Use the socket wrench
or nut driver.
c)
Connect the other ends of the two wires to the Return battery terminal.
7.
Make sure that you have correctly connected the battery to the PEM. Do this by using a
multimeter to measure the resistance between disconnected PEM wire leads and the Battery
Return pole.
For all the PEM wired leads, one at a time:
a)
At the battery, disconnect a PEM wire lead from the battery.
b)
Connect one multimeter probe to the battery Return and the other probe to the PEM wire
lead.
A very large resistance (indicating an open circuit) shows that the wire lead is
connected to the PEM
-48/-60VDC
terminal.
A very low resistance (indicating a closed circuit) shows that the wire lead is connected
to the PEM
Return
terminal.
c)
Reconnect the PEM wire lead to the battery.
8.
At the PEM:
a)
Attach the protective plastic cover.
b)
Set all the circuit breakers to ON.
9.
Do step 2 to step 8 for the second PEM.
10.