The installation of the Trifecta Pro Series should be done in
the following order:
1 Place Trifecta Pro Series Skid on concrete pad next to
bulk tank — concrete pad specifications should be in
conformance with local building codes and reviewed by
a licensed engineer
2
Pipe Trifecta Pro Series liquid fill line to bulk tank
labeled “From Bulk Tank.”For maximum efficiency, this
line should be insulated and no smaller that 3/4”
a Use liquid withdrawal line on bulk tank
Note:
Do not use the dip tube line.
3 Pipe Trifecta Pro Series gas use line to external
vaporizer labeled “To Vaporizer ” To minimize ice
build-up on pipe, this line should be insulated.
4
Connect power supply to dedicated 120V AC, 15 amp
circuit Connect ethernet cable
5 Commission Trifecta Pro Series System
Placement of Trifecta Pro Series
Skid
The Trifecta Pro Series skid has four lifting lugs on the top
of the skid These lifting lugs allow for placement of the skid
by overhead crane. If an overhead crane is not available, the
skid has fork truck access as well
Note:
The Trifecta Pro Series assembly weighs
almost 1900 lbs. empty (864 kg).
The Trifecta Pro Series skid should be placed on the concrete
pad near the bulk storage tank as seen in the Introduction
portion of this manual The skid should be placed as close to
the bulk tank as possible without interfering with any other
equipment or service requirements of the tank The system
requires a transfer of liquid and gas between the bulk storage
tank and the Trifecta Pro Series skid This process becomes
less efficient with increasing transfer line length.
Note:
Each site may have unique requirements;
however, it is recommended to follow the
basic layout located in the Introduction
section of this manual.
The skid should also be placed such that there is easy access
to all sides of the unit The skid should be placed where it
may receive a maximum amount of sunlight and airflow. One
must be able to check the individual cylinder gauges, the
control box, and any of the solenoid valves or transmitters at
any time Consideration should also be given to the external
vaporizer placement on the concrete pad
Note:
It is important that the sun and wind
contact both the external vaporizer and
pressure build coils inside the skid to
insure optimal operation of the unit and
prevent unusual buildup of ice.
Note:
Do not locate the Trifecta or Vaporizer
near equipment that produces excessive
moisture (i.e. cooling towers, drains, etc.).
Liquid Line Piping to Bulk Tank
The Trifecta Pro Series skid requires a liquid line piped from
the bulk storage tank This line will serve two functions
First, to allow the high pressure gas to return to the liquid
side of the bulk tank (reduce losses), second, to allow the
transfer of liquid from the bulk tank to the Trifecta By
removing the tube connection between A and B — shown
in Fig 1 on next page — the high-pressure vent gas can be
separately piped to the gas phase of the bulk tank, or totally
vented to atmosphere Venting the Trifecta to the gas phase is
often useful when connecting multiple Trifectas to one bulk
tank
The backside (PB Side) of the Pro Series skid has two/three
connection points
• Connection (A) serves as both the high pressure gas
outlet and the liquid inlet when the tubing connection
between A and B is in place
• Connection (B) is the high pressure gas outlet when the
tubing connector between A and B has been removed
• Connection (C) is the high pressure liquid outlet to the
process vaporizers
Installation
Содержание Trifecta Pro Series
Страница 2: ......
Страница 20: ...16 Installation Product Manual Trifecta Pro Series...
Страница 28: ...24 Operation Product Manual Trifecta Pro Series Mode 0 Figure 1 Filling Mode Vent to Storage...
Страница 29: ...25 Operation Product Manual Trifecta Pro Series Mode 0 Figure 2 Filling Mode Vent to Atmosphere...
Страница 30: ...26 Operation Product Manual Trifecta Pro Series Mode 0 Figure 3 Filling Mode Liquid Flow...
Страница 31: ...27 Operation Product Manual Trifecta Pro Series Mode 0 Figure 4 Filling Mode Low Loss...
Страница 32: ...28 Operation Product Manual Trifecta Pro Series Mode 0 Figure 5 Filling Mode Low Loss Vent to Atmosphere...
Страница 33: ...29 Operation Product Manual Trifecta Pro Series Mode Switch 0 to 1 Figure 6 Fill Mode Termination...
Страница 35: ...31 Operation Product Manual Trifecta Pro Series Mode Switch 1 to 2 Figure 8 Secondary Maintains Hold Pressure...
Страница 36: ...32 Operation Product Manual Trifecta Pro Series Figure 9 Primary Pressure Build Mode 2...
Страница 37: ...33 Operation Product Manual Trifecta Pro Series Figure 10 Primary PB Off Mode 2...
Страница 38: ...34 Operation Product Manual Trifecta Pro Series Figure 11 Call for Assist Mode Switch 2 to 3...
Страница 39: ...35 Operation Product Manual Trifecta Pro Series Figure 12 Secondary Assist of Primary Assist Mode 3...
Страница 40: ...36 Operation Product Manual Trifecta Pro Series Mode Switch 3 to 2 Figure 13 Assist Complete Primary Restored...
Страница 44: ...40 Operation Product Manual Trifecta Pro Series...