Page. 34 of 73
Training manual :PIGMA Gal Evo
4.5.2
Post-circulation.
4.6
DRAIN PORT & PLUG
Drainage of primary cicuit is possible by removing the plug
from the drain hole at the bottom of the hydraulic assembly of
boiler. The plug can be screwed out by use of a hexagon
head wrench size 9.
Post-circulation after:
3 way valve
position
Time of post circulation
Speed pump
Switching off due to:
Room thermostat opening
Heating
3 min
(set by parameter 237
beetwen 0 e 15’)
Low
Heating Off by Summer/Winter
button
Heating
3 min
(set by parameter 237
beetwen 0 e 15’)
Low
NTC delivery > T set +4
Heating
continuasly
Low
NTC return > 62°C or 67°C
Sanitary
continuasly
High
End of sanitary demand
Sanitary
Par. 254=0
30 sec
if:Tdel<75°C ;
3 min
if Tdel>75°C;
Post circulation: 30sec
High
Par. 254=1
3 min
End of comfort cycle
Sanitary
30 sec
High
End of antifreeze function
Heating /
Sanitary
2 min
High
End of chimney sweeping
function
Heating
1 min
Low
Solar sensor
Sanitary
30 sec
Low
Errors
Pressure sensor (102), Low
pressure (108, 111)
Heating
40 sec
Low
No circulation (103, 104, 105,
106, 107)
Heating
1 min
High
Flame missing, flame lift
(501, 504)
Heating
2 min
Low
Overheat (101), Thermo fuse
opening (610)
Heating
2 min
Low
No circulation (1P1, 1P2, 1P3)
Heating
10 sec
High
Floor thermostat opened (116)
Heating
90 sec
Low
Содержание PIGMA Gal Evo
Страница 10: ...Page 10 of 73 Training manual PIGMA Gal Evo...
Страница 52: ...Pag 52 de 73 Manuale Didattico ACO Training manual PIGMA Gal Evo...
Страница 56: ...Pag 56 de 73 Manuale Didattico ACO Training manual PIGMA Gal Evo 6 1 1 Diagramme lectronique FF boiler...
Страница 57: ...Pag 57 de 73 Manuale Didattico ACO Training manual PIGMA Gal Evo...
Страница 58: ...Pag 58 de 73 Manuale Didattico ACO Training manual PIGMA Gal Evo 6 1 2 Diagramme lectronique CF boiler...