6
Warning
GB
Product description
Flue connection
The boiler must be connected to a flue that conforms to the applicable
regulations. Check the exhaust gases are correctly evacuated and
measure the CO2 content at normal thermal flow. This value must not
exceed the value indicated in the TECHNICAL SPECIFICATIONS table. If
this value is greater than the value in the table, perform an efficiency
test of the flue. If you are unable to reduce the max CO2 value to the
values indicated in the TECHNICAL SPECIFICATIONS table, do not start
the appliance.
Important
Ensure the exhaust and ventilation passages are not obstructed.
Ensure the flue ducting is not leaking.
Electrical connection
For greater safety, the electrical installation should be thoroughly
checked by a qualified professional.
The manufacturer shall not be held liable for any damage caused by
an installation which has not been earthed or by faults in the electri-
cal supply.
Ensure that the installation is suited to the maximum power consu-
med by the boiler, indicated on the data plate.
The electrical connection must be made using a fixed connection (do
not use portable sockets) and fitted with a bipolar switch with a mini-
mum contact opening of no less than 3 mm.
Ensure that the cable cross-section is greater or equal to 0.75 mm2.
It is essential to connect the appliance to an efficient earth system to
guarantee the safety of the appliance.
Connect the supply cable provided to a 230V-50Hz network and en-
sure that the L-N polarisation and earth connection are correct.
Warning: If the power supply cable is damaged, it should be re-
placed by the manufacturer, the after-sales service or a person
with a similar status, in order to avoid potential danger.
Multiple sockets, extensions and adapters are prohibited.
It is prohibited to use gas, heating or hydraulic installation pipes to
earth the appliance.
The boiler is not protected against lightning.
If the fuses need to be changed, use fast-acting fuses.
H05V2V2-F
120
140