Cetetherm Midi Compact TA
Installation, service and operating instruction
32
11.3 Operation data Midi Compact 160
Primary side
Heating
DHW
Design pressure PS
16 Bar
16 bar
10 Bar
Design temperature TS
120°C
100°C
100°C
Relief pressure safety-valve
-
3 Bar
9 Bar
Volume Heat exchanger, L
4,1/2,27 L
4,1 L
2,16 L
CB60-80L
Temperature
program (°C)
Heating
Capacity CB
Plates Plates
Plates
Flow P dPp Flow S dPs
kW
type
no
primary
secondary
l/s
kPa
l/s
kPa
100-63/60-80
162
60
80
1*39L
1*40L
1,09
2,7 1,97
8,7
100-63/60-80 (62,8)
160
60
80
1*39L
1*40L
1,07
2,7
1,95
8,5
100-58/55-75
162
60
80
1*39L
1*40L
0,96
2,2
1,97
8,8
100-58/55-75 (57,2)
160
60
80
1*39L
1*40L
0,93
2,1
1,95
14,9
100-53/50-70 (51,9)
164
60
80
1*39L
1*40L
0,86
1,8
1,98
8,9
100-53/50-70 (51,9)
160
60
80
1*39L
1*40L
0,83
1,7
1,94
8,6
100-48/45-60 (45,6)
122
60
80
1*39L
1*40L
0,58
0,9
1,97
8,9
100-43/40-60 (41,4) 163
60
80
1*39L
1*40L
0,71
1,2 1,97
9,0
100-43/40-60 (41,4)
160
60
80
1*39L
1*40L
0,68
1,1
1,93
8,7
100-43/40-70
144
60
80
1*39L
1*40L
0,63
1,0
1,16
3,3
100-43/40-80
56
60
80
1*39L
1*40L
0,24
0,2
0,34
0,3
100-36/33-40 (33,0)
57
60
80
1*39L
1*40L
0,22
0,2
1,96
9,1
100-33/30-60
181
60
80
1*39L
1*40L
0,67
1,1
1,45
5,1
CB60-44L 2V
Temperature
program (°C)
DHW
Capacity CB
Plates Plates
Plates
Flow P dPp Flow S dPs
kW
type
no
primary
secondary
l/s
kPa
l/s
kPa
80-23/10-60 (19,1)
174
60
44
2*12L
1*12L+1*13L 0,75
20,5 0,83
33,2
80-23/10-60 (18,0)
146
60
44
2*12L
1*12L+1*13L 0,63
14,5 0,70
24,2
80-23/10-55 (16,1)
154
60
44
2*12L
1*12L+1*13L 0,67
15,2 0,82
32,8
80-23/10-55 (15,4)
132
60
44
2*12L
1*12L+1*13L 0,57
11,1 0,70
24,4
70-25/10-55 (19,8)
156
60
44
2*12L
1*12L+1*13L 0,85
24,2 0,83
33,2
70-25/10-55 (18,7)
132
60
44
2*12L
1*12L+1*13L 0,72
17,0 0,70
24,2
70-22/10-55 (19,8)
156
60
44
2*12L
1*12L+1*13L 0,80
24,2 0,83
33,2
70-22/10-55 (18,7)
132
60
44
2*12L
1*12L+1*13L 0,67
17,0 0,70
24,2
65-22/10-55
139
60
44
2*12L
1*12L+1*13L 0,79
26,0 0,74
26,6
65-22/10-55 (21,6)
132
60
44
2*12L
1*12L+1*13L 0,75
21,6 0,70
24,0