26
9.2 Clean the heating circuit strainer
Service actions must be carried out by an authorized service technician.
Before starting out repairs, close the shutoff valves
DH supply
,
DH return
,
heating supply and
heating return
.
Release the pressure using the heating circuit safety valve.
After finishing repair, fill up the heating circuit and vent.
Then open the shutoff valves, start with
heat return
and then
supply
, after that open
DH supply
and then the
return
line, to avoid pollutions in the system.
Open the valves slowly to avoid pressure surges.
1. Disconnect the power supply to the substation.
2. Close the shut-off valves.
3. Use a wrench and release the strainer holder and
remove the cartridge.
4. Clean the strainer in water and refit the cartridge. Screw
the strainer holder with a momentum of 10-20 Nm.
5. Fill up the heating circuit using the toping up valve, vent
the heating circuit.
6. Open the shutoff valves and connect the power supply to
the substation.
9.3 Change the complete DHWC pump or pump components
Maintenance and repairs must be carried out by an authorized service technician.
Before starting out repairs, close the shutoff valves
DH supply
,
DH return
,
cold-water
and
hot
water
. Note the setting of the balancing valve, then close it.
Release the pressure using the DHWC safety valve.
After finishing repair; fill up the hot water circuit and vent.
Open the shutoff valves, start with
DH Supply
and then
DH return,
to avoid pollutions in the
system. Open the valves slowly to avoid pressure surges.
Check the DHWC circulation.
Change the complete pump or just the pump motor.
1. Disconnect the power supply to the substation, disconnect
the power cable to the pump.
2. Close the shut-off valves and the balancing valve.
3. Choose alternative a or b.
a) When changing the complete pump, release the brass
nuts with a wrench and replace the pump.
Connect the pump cable.
b) Only changing the motor, release it by unscrewing
four socket head cap screws and replace the motor.
Connect the pump cable.
4. Open the shut-off valves cold-water and hot water.
5. Open and adjust the balancing valve.
6. Vent the circuit by opening a hot water tap.
Picture 19