Cetetherm Midi Compact TA
Installation, service and operating instruction
19
7 Service instructions
To avoid the risk of scalding, make sure that no-one draws any water while servicing the
substation.
Grey marked service actions must be carried out by an authorized service technician.
Note!
Make sure that the substation has been correctly installed.
7.1 Service instructions, tap water
7.1.1 Tap water temperature too low
Reason
Action
District heating supply too low
Check the primary inlet temperature
The temperature can be checked by means of the energy meter
(min 65º C) or at the district heating medium supply.
Handle on control valve incorrectly
positioned
Adjust the handle on the control valve
Adjust the tap water temperature by turning the handle clockwise
for increased and anti-clockwise for decrease temperature.
Turn the handle until the desired temperature is reached (55º C
approx.). The stabilisation time for the hot water temperature is
about 20 seconds.
District heating strainer clogged
See
9.1 Cleaning the district heating strainer
Hot water valve and/or actuator does
not work
See
Check the function of the hot water valve and actuator
7.1.2 Tap water temperature too high
Reason
Action
Handle on control valve incorrectly
positioned
Adjust the handle on the control valve
Adjust the tap water temperature by turning the handle clockwise
for increased and anti-clockwise for decrease temperature.
Turn the handle until the desired temperature is reached (55º C
approx.). The stabilisation time for the hot water temperature is
about 20 seconds.
Hot water valve and/or actuator does
not work
See
Check the function of the hot water valve and actuator.
7.1.3 Hot water temperature unstable
Reason
Action
Alternating pressure on primary side
Check available differential pressure and temperature at the
district heating medium supply
.
The temperature can be checked by means of the energy meter,
minimum 65ºC, or at the district heating medium supply.
District heating strainer clogged
See
9.1 Cleaning the district heating strainer.
DHWC pump is not running
Check that the electrical power is on
See