Cetetherm Midi Compact TA
Installation, service and operating instruction
27
7. Connect the power supply to the substation.
8. Open the shutoff valves DH Supply and then DH return.
9.4 Change the complete heating pump or pump components
Maintenance and repairs must be carried out by an authorized service technician.
Before starting out repairs, close all shutoff valves
Release the pressure using the heating safety valve.
After finishing repair; fill up the
heating circuit
and vent.
Open the shutoff valves, start with
heating return
and then
heating supply
, then
DH Supply
and
DH return,
to avoid pollutions in the system.
Open the valves slowly to avoid pressure surges.
Change the complete pump or just the pump head.
1. Disconnect the power supply to the substation and the pump.
2. Close the shut-off valves.
3. Choose alternative a or b.
a) When changing the complete pump, release the brass nuts
with a wrench and replace the pump.
Connect the pump cable.
b) Only changing the pump head
Loosen the screw in the clamp that holds the pump head
and pump housing together.
Mount a new pump head, fit and tighten the screw that
holds the clamp to 8 Nm ± 1 Nm.
NOTE! Do not retighten the screw if condensed water is
dripping from the clamp.
4. Fill up the heating circuit using the top up valves. Vent the
heating circuit.
5. Open the shut-off valves and connect the power supply to the
substation.
9.5 Change the actuator
Maintenance work must be carried out by an authorized service technician.
Disconnecti the power supply to the pump and the substation.
1. Lower the operation handle on the actuator to stop the motor.
2. Remove the lid from the actuator, put a screwdriver under the lid
lock and press gently. Disconnect the wiring- note where they are
connected.
3. Loosen the screws on the brace that holds the actuator to the
valve, lift off the actuator.
Note!
The valve can be very hot
Picture 21