CET Electric Technology
94
12)
Recommended Pulse Constant settings for the different Line Voltage &
Current
Inputs
Voltage Input
Current Input
X Value
Energy Pulse Constant (X Value)
69V/120V
1A
4
0=1000 imp/kWh
1=3200 imp/kWh
2=5000 imp/kWh
3=6400 imp/kWh
4=12800 imp/kWh
5A
4
240V/415V
1A
4
5A
1
400V/690V
1A
2
5A
0
Table 5-37 Pulse Constant
13)
The
Self-Read Time
applies to both the Peak Demand Log as well as the Max./Min. Log and supports the following three options:
•
A zero value means that the Self-Read will take place at 00:00 of the first day of each month.
•
A non-zero value means that the Self-Read will take place at a specific time and day based on the formula:
Self-Read Time
= (Day
x 100 + Hour) where 0 ≤ Hour ≤ 23 and 1 ≤ Day ≤ 28. For example, the value 1512 means that the Self-Read will take place at
12:00pm on the 15th day of each month.
•
A 0xFFFF value means the automatic self-read operation is disabled and the log will be transferred manually.
14)
SNTP doesn’t support Daylight Saving Time (DST). The following table lists the supported Time Zones:
Code
Time Zone
Code
Time Zone
0
GMT-12:00
17
GMT+3:30
1
GMT-11:00
18
GMT+4:00
2
GMT-10:00
19
GMT+4:30
3
GMT-9:00
20
GMT+5:00
4
GMT-8:00
21
GMT+5:30
5
GMT-7:00
22
GMT+5:45
6
GMT-6:00
23
GMT+6:00
7
GMT-5:00
24
GMT+6:30
8
GMT-4:00
25
GMT+7:00
9
GMT-3:30
26
GMT+8:00
10
GMT-3:00
27
GMT+9:00
11
GMT-2:00
28
GMT+9:30
12
GMT-1:00
29
GMT+10:00
13
GMT-0:00
30
GMT+11:00
14
GMT+1:00
31
GMT+12:00
15
GMT+2:00
32
GMT+13:00
16
GMT+3:00
Table 5-38 Time Zones
15)
This string register specifies the sender email address that appears in the “From” field of the email. This string may be up to 35
characters long. Please add the value zero “0000” at the end of the string as the string terminator. For example, the default sender
email address is
, set the registers as” 0073 0065 006E 0064 0065 0072 0040 0064 006F 006D 0061 0069 006E
002E 0063 006F 006D 0000”.
16)
This string register specifies the Logon Password to login the “Source Email” account. This string may be up to 19 characters long.
Please add the value zero “0000” at the end of the string as the string terminator. For example, the default password is “iMeter6”, set
the registers as “0069 004D 0065 0074 0065 0072 0036”
17)
This string register specifies the receiver email address that appears in the “To” field of the email. This string may be up to 35 characters
long. Please add the value zero “0000” at the end of the string as the string terminator. For example, the default receiver email address
is
, so set the registers as” 0072 0065 0063 0065 0069 0076 0065 0072 0040 0064 006F 006D 0061 0069 006E
002E 0063 006F 006D 0000”.
18)
The Backlight Time-out can be set from 0 to 60 minutes. A zero (0) value indicates that the backlight time-out is disabled.
19)
The Interval Energy will be reset once the
EN Period
is changed.
20)
Port 80 and 443 is used for HTTP, HTTPS connection with the web server, respectively. When set other values to the port number,
HTTPS is the only supported connection.
21)
The
Delimiter
setup register supports two options, 0 and 1:
0: “,” is used as the x1000 delimiter and “.” as the decimal point (e.g. 123,456,789.0).
1: “ ” is used as the x1000 delimiter and “,” as the decimal point (e.g. 123 456 789,0).
5.10.2
Setpoint Setup
5.10.2.1
Setpoint Setup Registers
Register
Property
Description
Format
6600~6609
RW
Setpoint #1 (Standard)
See Section
6610~6619
RW
Setpoint #2 (Standard)
6620~6629
RW
Setpoint #3 (Standard)
6630~6639
RW
Setpoint #4 (Standard)
6640~6649
RW
Setpoint #5 (Standard)
6650~6659
RW
Setpoint #6 (Standard)
6660~6669
RW
Setpoint #7 (Standard)
6670~6679
RW
Setpoint #8 (Standard)
6680~6689
RW
Setpoint #9 (Standard)