CET Electric Technology
95
6690~6699
RW
Setpoint #10 (Standard)
6700~6709
RW
Setpoint #11 (Standard)
6710~6719
RW
Setpoint #12 (Standard)
6720~6729
RW
Setpoint #13 (Standard)
6730~6739
RW
Setpoint #14 (Standard)
6740~6749
RW
Setpoint #15 (Standard)
6750~6759
RW
Setpoint #16 (Standard)
6760~6769
RW
Setpoint #17 (High-Speed)
6770~6779
RW
Setpoint #18 (High-Speed)
6780~6789
RW
Setpoint #19 (High-Speed)
6790~6799
RW
Setpoint #20 (High-Speed)
6800~6809
RW
Setpoint #21 (High-Speed)
6810~6819
RW
Setpoint #22 (High-Speed)
6820~6829
RW
Setpoint #23 (High-Speed)
6830~6839
RW
Setpoint #24 (High-Speed)
Table 5-39 Setpoints Setup
5.10.2.2
Setpoint Setup Data Structure
Offset
Property
Description
Format
Range
Default
+0
RW
Standard
Setpoint
Type
UINT16
0=Disabled
1=Over Setpoint
2=Under Setpoint
0
+1
RW
Parameter
UINT16
1 to 35
1
+2
RW
Active Limit
INT32
-
999999
+4
RW
Inactive Limit
INT32
-
999999
+6
RW
Active Delay
UINT16
0 to 9999 s
10
+7
RW
Inactive Delay
UINT16
0 to 9999 s
10
+8
RW
Trigger 1
UINT16
0 to 22
0
+9
RW
Trigger 2
UINT16
0 to 22
0
+0
RW
High-speed
Setpoint
Type
UINT16
0=Disabled
1=Over Setpoint
2=Under Setpoint
0
+1
RW
Parameter1)
UINT16
1 to 14
1
+2
RW
Active Limit
INT32
-
999999
+4
RW
Inactive Limit
INT32
-
999999
+6
RW
Active Delay
UINT16
0 to 9999 cycles
10
+7
RW
Inactive Delay
UINT16
0 to 9999 cycles
10
+8
RW
Trigger 1
UINT16
0 to 22
0
+9
RW
Trigger 2
UINT16
0 to 22
0
Table 5-40 Setpoint Setup Register Structure
Notes:
1)
“
Parameter
” specifies the parameter to be monitored.
The table below provides a list of Setpoint Parameters.
Standard Setpoint can
monitor all parameters while the HS Setpoint only can monitor 1 to 14.
Key
Parameter
Scale/Unit
1
Uln
x100, V
2
Ull
x100, V
3
I
x1000, A
4
x1000, A
5
Freq Deviation
x100, Hz
6
kW Total
kW
7
kvar Total
kvar
8
PF
x1000
9
DI1
1)
For Over Setpoint, the Active Limit is DI Close (
DI=1
), and Inactive Limit is DI
Open (
DI=0
);
2)
For Under Setpoint, the Active Limit is DI Open (
DI=0
), and Inactive Limit is
DI Close (
DI=1
).
10
DI2
11
DI3
12
DI4
13
DI5
14
DI6
15
AI
/
16
kW Total Present Demand
kW
17
kvar Total Present Demand
kvar
18
PF Present Demand
x1000
19
Total kW Predicted Demand
kW
20
Total kvar Predicted Demand
kvar
21
PF Predicted Demand
x1000