2.5.5
3-Phase 3-Wire Direct Delta Connection with 3CTs or 2CTs
Please consult the Serial Number Label to ensure that the rated Ull voltage is less than or equal to the meter’s rated
Line
voltage input specification. Set the
Wiring Mode
to
3P3W
.
Figure 2-10 3P3W Direct Connections with 3 CTs
Figure 2-11 3P3W Direct Connection with 2CTs
2.5.6
3-Phase 3-Wire Open Delta with 2PTs and 3CTs or 2CTs
Please consult the serial number label to ensure that the rated PT secondary voltage is less than or equal to the meter’s
rated
Phase
voltage input specification. Set the
Wiring Mode
to
3P3W
.
Figure 2-12 3P3W Open Delta with 2PTs & 3CTs
Figure 2-13 3P3W Open Delta with 2PTs & 2CTs
2.6
Communications Wiring
2.6.1
RS485 Port
The iMeter 6 provides one RS485 port and supports the Modbus RTU protocol. Up to 32 devices can be connected on a
RS485 bus. The overall length of the RS485 cable connecting all devices should not exceed 1200m.
If the master station does not have a RS485 communications port, a RS232/RS485, USB/RS485 or Ethernet/RS485
converter with optically isolated outputs and surge protection should be used.
The following figure illustrates the RS485 communications connections on the iMeter 6:
Figure 2-14 RS-485 Communications Connections