C650 & C650R User
Manual Page 15
3.3
MECHANICAL INSTALLATION
3.3.1 Tower model
To keep air flowing freely, it is recommended to keep a clearance with 500mm space both at the front and
rear side of the UPS.
UPS model
1.Place the unit on a flat, stable surface in its final location,
2.Install ‘tower foot’ (if configured): remove side’s screw from the unit, then install ‘tower foot’.
3.Install the unit to ground(optional): place 4pcs bolts (M8 is recommended) to the final location, bolt’s position
please refer to below, then fix the unit to the bolts.
EBM Model
EBM installation steps are the same as UPS as above.
It is recommended to place EBM modular to UPS’s left side.
3.3.2
Rack model
Rack models support 2 installation modes: Rack installation and Tower installation.
1. To keep good ventilation, please keep a free space of at least 500mm at least at the front & rear panels of
modules.
2. Do not carry by the front or rear panel of the module during installation.
RACK INSTALLATION
This procedure is suitable for 19-inch rack cabinet installation, it is recommended that the depth of the cabinet be
no less than 800mm.
UPS model
Identify the final position and keep ‘2U’ space for this
installation.
1.Install the rail kit (if configured). This rail kit is '2U & with screw
holes (M5)', the depth of the rail kit is: 443-773 mm.