C650 & C650R User
Manual Page 39
Operating Temperature
0-40
⁰
C (derating 50% above 40
⁰
C) excluding batteries
Relative Humidity
0-95% (non-condensing)
Operating Altitude
0-3000m (the load derating 1 % every up 100m @1000~3000m)
Storage temperature (with battery)
-15
⁰
C - 40
⁰
C
Storage temperature (without battery)
-25
⁰
C - 55
⁰
C
Certification
CE, IEC/EN 62040, UKCA
Rack UPS
Model
C650R-060-B
C650R-060-C
C650R-100-B
C650R-100-C
Capacity
6kVA/6kW
10kVA / 10kW
INPUT
Input Voltage Range
110VAC - 276VAC
Rated Voltage
220/230/240VAC
Frequency
50Hz/60Hz
Frequency Range
45Hz-55Hz (50Hz system), 54Hz-66Hz (60Hz system) @ load>60%
Power Factor
1
Rated current
35A
45A
54A
63A
OUTPUT
Voltage Regulation (AC Mode)
220/230/240V AC
Rated Frequency
50 Hz / 60 Hz
AC Outlets
Terminal Block
Maximum Power Factor
1
Voltage accuracy
±1%
Transfer Time Line <-> Battery
0ms
Transfer Time INV<-> Bypass
0ms
Wave form
Pure sine wave
Short Circuit Current on Normal Mode
54A for 200ms max
113A for 200ms max
Overload Capacity
105%-125% Load, 10 minutes transfer to Bypass;
125%-150% Load, 30 seconds transfer to Bypass;
>150% Load, 0.5 seconds transfer to Bypass
BATTERY
Voltage
192 / 240V DC selectable