8
1.3.6. OPTIONS
1.3.6.1. BOILER SETTINGS
- in this menu are shown settings for temperature and flue gas fan rpm sensors and
options to disable/enable them
NOTE: to change this options, user PIN must be entered
(PIN = USR)
EXAMPLE - how to enter PIN
PIN enter screen
go to the parameter you
want to change
press button
press button
with
/
buttons
enter 1st PIN symbol
press button to
confirm it and jump to
2nd PIN symbol
with
/
buttons
enter 2nd PIN symbol
press button to
confirm it and jump to
3rd PIN symbol
with
/
buttons
enter 3rd PIN symbol
press button to
confirm it and enter to
value change screen
NOTE:
to go back from 3rd to 2nd and
from 2nd to 1st PIN symbol
press button
also, to cancel PIN entering
press button until exit the
menu
VALUE CHANGE screen
with / buttons
change the value
with button confirm it
with button cancel it
BY DISABLING ONE OR MORE SENSORS IN THIS MENU BOILER ENTERS ’’INTERVENTION WORK’’
-
FLUE GAS FAN RPM SENSOR - DISABLED
- boiler will work in INTERVENTION WORK if flue gas fan is working, set
flue gas fan rpm is shown as % in relation to max. fan speed
-
FLUE GAS TEMP. SENSOR - DISABLED
- boiler will work in INTERVENTION WORK without flue gas temperature
control (use only in emergency because there isn’t flue gas fan protection against to high temp.), flue gas temp. is NOT
shown on screen
-
DHW TANK SENSOR - DISABLED
- DHW pump (P2) will work allways, DHW temp. is NOT shown on screen
-
ACCUMULATION TANK UPPER SENSOR - DISABLED
- boiler will work in INTERVENTION WORK without upper
accumulation tank sensor control, pump P1 will work without control by upper accumulation tank temperature,
upper accumulation tank temp. is NOT shown on screen
Options
Technical instructions REGULATION
BioTec-C