14
Boiler working stages
NOTE:
- after enabling protection valve, new menu will be shown automatically. In this menu opening/closing time of 3-way
mixing valve actuator must be set. Set time depends of installed actuator.
2. press UP button
2
3. press OK button
- boiler fan will start -
3
1. press OK button
1
3.1. BOILER WORKING STAGES
Procedure for boiler start:
1. IGNITION STAGE AND FIRST FILLING
1 - open upper boiler door (and close lower boiler door if they are open).
2 - switch on main switch (if it was switched off).
3 - on control panel press OK button, on screen STAR/STOP switch with OFF position will appear, press right
button to switch it to START position and confirm it with OK button - regulation will enter S stage (start stage)
and flue gas fan start to work, on screen, normal view and startup view will be switching.
4 - cover the refractory stone with one row of wood logs (be careful to not plug hole on refractory stone (detail A).
5 - cover the wood logs with fine chopped wood (use enough fine chopped wood to cover wood logs below).
6 - height of fine chopped wood layer must conform a approx. height of first row of wood logs
7 - cover the fine chopped wood with crumped paper (use enough crumpled paper to cover fine chopped wood)
(detail B).
8 - place the wood logs on crumpled paper.
9 - fill the fuel loading chamber with wood logs (detail C).
10 - close upper and lower doors.
11 - leave middle door opened.
12 - ignite the fire throuh middle boiler door (detail C).
13 - after few minutes, after fine chopped wood is on fire close middle boiler door.
14 - press OK button again to enter next working stage C (stabilisation).
15 -
only BioTec-C 25
- set button RP to the max. position, or to the position based on the individual expirience
according to used wood (this button is not related with the regulation).
16 -
only BioTec-C 25
- leave button RP to the previously set position at least 1 hour or maximum to the next
wood loading cycle.
Upper procedure is related to the start/stabilisation stages from cold start (with GLOW mode disabled).
This procedure must be done always at cold start or when there isn’t enough glow and wood filling is wanted.
3.0. USING THE BOILER
3.1.1. S - STAGE (IGNITION)
Technical instructions REGULATION
BioTec-C