31
V3.15.22
Remote Control / Display Instructions
Digital
Display
The temperature displayed
on the control is red instead of
blue.
Set Button
The cooling unit is factory
preset with a Minimum Set
Point of 58°F and a
Temperature Differential
of 4°F.
This means that the cooling unit will turn on when the display rises above 62°F
(58°F + 4°F), and turn off when the display falls below 58°F. In this example,
the average temperature inside the cellar will be 60°F. To view the Minimum
Set Point, press the “Set” button for one second.
To change the Minimum Set Point,
Press the “Set” button for three seconds until °F” blinks
Press “Up” or “Down” button
Press “Set” button to confirm
The “Set” temperature will blink three times to indicate confirmation
The recommended Minimum Set Point range is 53 - 60°F. To change the
Temperature Differential, see “Advanced Operation” later in this chapter.
Quick Chill
Button
Button
Icon
To activate the “Quick Chill” mode, press the “Up” button for 3 seconds
To deactivate “Quick Chill”, press the “Up” button for 3 seconds again
The “Quick Chill” indicator (Row 3) light will turn on when the cooling unit is in
“Quick Chill” mode,
In the “Quick Chill” mode, the cooling unit will run continuously for 6 hours (or
until the unit reaches set point.). This mode is useful after loading “warm”
bottles in the cabinet.
Auto Defrost
Mode
The cooling unit has a factory default defrost cycle that initiates every 16 hours
for 20 minutes. When the cooling unit is in auto-defrost mode, the “Defrost”
Indicator light (Top row) will turn on, and the evaporator fan will run.
Manual Defrost
Hold the defrost button in for 3 seconds to initiate a manual defrost. The
“Defrost” Indicator light (Top row) will turn on for a 20 minute defrost cycle.
Light
The light button function is disabled, however pressing it will turn on/off the light
indicator on the display (2nd row).
Energy Saver
The remote display is not configured with an Energy Saver mode. The set
point can be raised manually for periods where energy savings is desired.