Plug in the Condensing Unit.  The Condensing Unit should turn on for a brief 
period, and then shut off.   

25. 

Plug in the Evaporator.  The controller should light up.  Turn the controller 
on so that a temperature value is displayed.  There is a 3 minute delay at 
start  up  indicated  by  a  blinking  snowflake  icon  on  the  display.    After  3 
minutes, a snowflake and fan icon should appear on the display, lit solid.  
The system is now in cooling mode.  Verify that the Condensing Unit has 
turned on, and that the Evaporator is producing cold air. 

 

 
Installation Tips and Guidelines  

 

  Make  sure  you  attach  the  line  set  hoses  in  the  sequence  described  in  the 

instructions 

  Make sure to plug in power cords in the sequence described in the instructions 

  Before attaching each connection, STOP and double-check that BLUE and RED 

female  connections  are  attached  to  corresponding  BLUE  and  RED  male 
connections  

  Inspect Evaporator and Condensing unit fans to confirm airflow.  There shouldn’t 

be any excessive vibration, noise or obstructions to airflow. 

  Do  not  leave  the  system  unattended  until  it  has  reached  normal  operating 

conditions,  and  the  system  has  been  observed  properly  cycling  on/off  to  the 
desired set point and differential. 

 

 

 

 

Summary 

Keep in mind the following guidelines before purchasing a wine cooling unit from 
CellarPro: 

  If  the  cellar  is  too  large  for  the  cooling  unit,  the  cooling  unit  will  be  unable  to 

maintain proper, even temperatures inside the cellar. 

  Without proper insulation and an airtight environment, the cooling unit effectively will 

become a de-humidifier and potentially will produce buckets of water. 

  If the condensing unit does not have access to cool air, either because of 

improper ventilation or because the environments is too hot, the cooling unit will 
be unable to maintain proper temperatures inside the cellar. 

Under  any  of  the  above  conditions,  the  unit’s  internal  components  may  become 
damaged,  the  expected  useful  life  of  the  wine  cooling  unit  may  be  adversely 
affected, and the product’s warranty may become null and void. 

 

 

 

Содержание 3000Shqc-EC

Страница 1: ...V3 15 22 ControltheElements QuickConnectSplitRefrigerationSystems Owner sManual...

Страница 2: ...2 V3 15 22 This page intentionally left blank...

Страница 3: ...f you still have questions please don t hesitate to contact your dealer or reach us directly at CellarPro Cooling Systems 1445 N McDowell Blvd Petaluma CA 94954 707 794 8000 x3 Email info cellarprocoo...

Страница 4: ...b l e o f C o n t e n t s I Package Contents 5 II Specifications and Cut Sheets 6 III Cellar Construction 9 IV Installation Instructions 11 V Operating Instructions 26 VI Troubleshooting 33 VII Limit...

Страница 5: ...sleeve 1 1 Butyl 18 in n a Adhesive backed foam strips 1 x 9 25 x1 5 x1 5 and 1 x 3 75 x1 5 x1 5 n a 1 Set Large tie wraps 2 2 Remote Display Kit 1 optional 1 optional Bottle Probe 1 optional 1 optio...

Страница 6: ...mounting bracket 63 0 50 5 6 4000Shqc EC 30 4 x 14 4 x 13 2 incl mounting bracket 65 0 50 7 9 Condensing Unit with Hood Model Dimensions W x D x H inches Weight lbs MCA 3000Sqc Shqc EC 19 4 x 23 3 x...

Страница 7: ...7 V3 15 22 Evaporator Cut Sheets...

Страница 8: ...8 V3 15 22 Condensing Unit Cut Sheet...

Страница 9: ...er recessed lighting which can allow air to leak into the cellar It is important that all walls joints doors and windows electrical outlets and or switches pipes vents and light fixtures be sealed to...

Страница 10: ...o the bottom of the cellar To ensure proper airflow and reduce temperature stratification inside the cellar the space in front of the cold air discharge should be clear of any obstructions including w...

Страница 11: ...r warranty does not cover damage from marine exposure within 5 miles of the ocean In these environments you will need an applied coating such as Insitu to protect against corrosion that is common in c...

Страница 12: ...ns 3000Sqc EC and 4000Sqc EC Connection locations are specified when ordering the equipment and are available in the following options Refrigerant connections rear or left side Power cord rear or left...

Страница 13: ...Shqc EC and 4000Shqc EC Connection locations are specified when ordering the equipment and are available in the following options Refrigerant connections rear or left side Power cord rear or left side...

Страница 14: ...V3 15 22 Evaporator Mounting Instructions 3000Sqc EC and 4000Sqc EC Mounting brackets which attach to the sides of the evaporator are provided to mount the evaporator flush to a wall inside the cella...

Страница 15: ...ches to the wall behind the evaporator is provided to mount the evaporators to the wall inside the cellar First the wall bracket is attached to the wall and then the evaporator slides onto the bracket...

Страница 16: ...again into an open drain Then fill the trap with water The condensate trap will allow any excess moisture inside the Evaporator to overcome the static pressure and flow out of the drain line Before pu...

Страница 17: ...he Condensing Unit turns on and off based on suction pressure as follows The Evaporator includes a factory installed liquid line solenoid valve LLSV which is controlled by the Evaporator temperature c...

Страница 18: ...18 V3 15 22 Wiring Diagram...

Страница 19: ...QuickConnect Line Set has sufficient length to interconnect the two units If the line set is not long enough do not proceed Contact CellarPro for immediate assistance 2 Reference the Evaporator Mount...

Страница 20: ...tion line connection to the male connection STOP AND MAKE SURE YOU ARE ATTACHING BLUE TO BLUE Hand thread at first to get the threads started without cross threading Once it is too hard to turn by han...

Страница 21: ...d wrap around the coupling provided that the seam is sealed tight Insulating the suction connection is essential to avoid condensation issues 8 Identify the Liquid line marked RED on the female connec...

Страница 22: ...nnections only It is important to keep the drain line level or below the point where it exits the evaporator as it passes through the cutout 11 3000Sqc EC 4000Sqc EC systems rear connections only Appl...

Страница 23: ...o the wall cutout and drywall trim around the connections as desired For serviceability do not use spray foam to insulate around the metal QuickConnect fittings 16 Route the drain line installing a tr...

Страница 24: ...onnection STOP AND MAKE SURE YOU ARE ATTACHING BLUE TO BLUE Follow the previous process to tighten the connection 22 Identify the Liquid line marked RED on the female connector 23 Identify the male Li...

Страница 25: ...nsing unit fans to confirm airflow There shouldn t be any excessive vibration noise or obstructions to airflow Do not leave the system unattended until it has reached normal operating conditions and t...

Страница 26: ...wine which tend to be much colder than storage temperatures especially serving temperatures for white and sparkling wines CellarPro cooling units must be used stored moved and or shipped in the uprigh...

Страница 27: ...ontroller is described in detail in the following section 2 Fan Speed Selector Switch Low Med High The cooling unit fans operate on 3 speed settings Low Medium and High For optimum sound and energy ef...

Страница 28: ...grill of the cooling unit Power On Off Press Power On Off to turn the unit on and off When the Compressor On indicator light is on the Compressor is running When the Fan On indicator light is on the F...

Страница 29: ...Differential of 4 F This means that the cooling unit will turn on when the display rises above 62 F 58 F 4 F and turn off when the display falls below 58 F In this example the average temperature ins...

Страница 30: ...re Differential is unchanged Quick Chill Button To activate the Quick Chill mode press the Up Quick Chill button for three seconds To deactivate Quick Chill press Quick Chill button for three seconds...

Страница 31: ...To activate the Quick Chill mode press the Up button for 3 seconds To deactivate Quick Chill press the Up button for 3 seconds again The Quick Chill indicator Row 3 light will turn on when the cooling...

Страница 32: ...ry preset ENERGY SAVINGS MODE DIFFERENTIAL The factory preset for this setting is 4 This setting controls the Temperature Differential for the Energy Savings Mode The recommended range for this settin...

Страница 33: ...lter is clean 3 Increase the supply of cool air to the space outside the condenser coils using a fan ducting or an exhaust system to remove heat from the space 4 Raise the Minimum Set Point on the coo...

Страница 34: ...eck for loose wires and reconnect Low pressure switch is open On Valve control systems make sure solenoid is energized Jumper out switch to check for a faulty switch and replace if necessary Note that...

Страница 35: ...re power Power supply to fan interrupted loose wire Inspect for loose fan wiring and reconnect Fan capacitor check for loose wires or out of spec capacitance Reconnect loose wires or replace capacitor...

Страница 36: ...op section Condensing unit never shuts off System is wired incorrectly Locate correct wiring diagram for Electronic or Valve controlled system trace wiring and correct If a Valve control system the lo...

Страница 37: ...first 23 hours of operation after the cooling unit is plugged in and or turned on The control panel also will flash a code for each alarm as follows Alarm What it means What to do P1 Probe 1 which sen...

Страница 38: ...ted warranty applies only to cooling units purchased from the factory or an authorized dealer Damage caused by others or by any cause beyond the control of CellarPro shall not be considered defects in...

Отзывы: