Outside the Cellar 

Condensing unit Air Exhaust.  

Condensing units create significant hot air which 

must  be  exhausted  into  an  appropriately-sized  space  in  order  for  the  heat  to 
dissipate. If the space is constrained and/or too small, the heat will not dissipate.  
In this event, the cooling unit will be forced to re-circulate its hot air exhaust and/or 
the static pressure will back up the cooling unit. If this happens, the cooling unit’s 
ability to create cold air inside the cellar will be compromised.   

Condenser Air Intake.  

The condenser coils require access to cool air in order for 

the cooling unit to produce cold air. In addition, the cooling unit must be installed 
so that, after its installation, the condenser coils are accessible for periodic cleaning.

 

The Condensing unit cannot be ducted. 

 

Inside the Cellar 

Evaporator Air Intake. 

 When the warm air passes across the evaporator coils, heat 

is removed from the air, and the resulting cold air is exhausted into the cellar. To 
ensure proper airflow, minimum clearance of 12” is required in front of the cooling 
unit.

 

Evaporator Air Exhaust. 

Cold air is exhausted at the top front of the cooling unit. 

Because CellarPro cooling units are located at the highest point inside wine cellars, 
the cold air exhaust eventually will drop to the bottom of the cellar. To ensure proper 
airflow and reduce temperature stratification inside the cellar, the space in front of 
the cold air discharge should be clear of any obstructions, including wine bottles, wine 
racks, etc. 

Ducting  For  the  Evaporator  (3000Sqc-EC/4000Sqc-EC  Models).   

Cold  air 

exhaust and return (from the evaporator) can be ducted with our front duct hood up 
to 100 equivalent feet of total ductwork, or 50 equivalent feet for both the discharge 
and  return  ducting,  using  8”  diameter  insulated  ducting.    Our  front  duct  kit  is 
compatible  exclusively  with  our  3000Sqc-EC  and  4000Sqc-EC  cooling  units.  If 
you’d like to duct one of our larger cooling units, please consider our AH6500 and 
AH8500 cooling units.   

Before attaching the front duct hoods, remove the front grill (if present) from the 
front of cooling unit. 

Front  duct  kits  should  be  paired  with  our  remote  control  panel,  which  allows  the 
digital display to be installed remotely from the cooling unit, either inside or outside 
the cellar.  The remote comes standard with 10’ of wiring, and offer additional wiring 
upon request.   Front duct kits also should be used with our remote thermostat (aka 
bottle probe), which comes standard with a 10 foot cord that can be plugged into 
the  cooling  unit,  and  terminate  inside  the  cellar  to  measure  either  air  or  liquid 
temperature.  Please note that the HY setting should be changed from the 4 to 1 if 
the  bottle  probe  will  be  inserted  in  liquid  (see  Advanced  Operation  for  more 
information). 

 

Содержание 3000Shqc-EC

Страница 1: ...V3 15 22 ControltheElements QuickConnectSplitRefrigerationSystems Owner sManual...

Страница 2: ...2 V3 15 22 This page intentionally left blank...

Страница 3: ...f you still have questions please don t hesitate to contact your dealer or reach us directly at CellarPro Cooling Systems 1445 N McDowell Blvd Petaluma CA 94954 707 794 8000 x3 Email info cellarprocoo...

Страница 4: ...b l e o f C o n t e n t s I Package Contents 5 II Specifications and Cut Sheets 6 III Cellar Construction 9 IV Installation Instructions 11 V Operating Instructions 26 VI Troubleshooting 33 VII Limit...

Страница 5: ...sleeve 1 1 Butyl 18 in n a Adhesive backed foam strips 1 x 9 25 x1 5 x1 5 and 1 x 3 75 x1 5 x1 5 n a 1 Set Large tie wraps 2 2 Remote Display Kit 1 optional 1 optional Bottle Probe 1 optional 1 optio...

Страница 6: ...mounting bracket 63 0 50 5 6 4000Shqc EC 30 4 x 14 4 x 13 2 incl mounting bracket 65 0 50 7 9 Condensing Unit with Hood Model Dimensions W x D x H inches Weight lbs MCA 3000Sqc Shqc EC 19 4 x 23 3 x...

Страница 7: ...7 V3 15 22 Evaporator Cut Sheets...

Страница 8: ...8 V3 15 22 Condensing Unit Cut Sheet...

Страница 9: ...er recessed lighting which can allow air to leak into the cellar It is important that all walls joints doors and windows electrical outlets and or switches pipes vents and light fixtures be sealed to...

Страница 10: ...o the bottom of the cellar To ensure proper airflow and reduce temperature stratification inside the cellar the space in front of the cold air discharge should be clear of any obstructions including w...

Страница 11: ...r warranty does not cover damage from marine exposure within 5 miles of the ocean In these environments you will need an applied coating such as Insitu to protect against corrosion that is common in c...

Страница 12: ...ns 3000Sqc EC and 4000Sqc EC Connection locations are specified when ordering the equipment and are available in the following options Refrigerant connections rear or left side Power cord rear or left...

Страница 13: ...Shqc EC and 4000Shqc EC Connection locations are specified when ordering the equipment and are available in the following options Refrigerant connections rear or left side Power cord rear or left side...

Страница 14: ...V3 15 22 Evaporator Mounting Instructions 3000Sqc EC and 4000Sqc EC Mounting brackets which attach to the sides of the evaporator are provided to mount the evaporator flush to a wall inside the cella...

Страница 15: ...ches to the wall behind the evaporator is provided to mount the evaporators to the wall inside the cellar First the wall bracket is attached to the wall and then the evaporator slides onto the bracket...

Страница 16: ...again into an open drain Then fill the trap with water The condensate trap will allow any excess moisture inside the Evaporator to overcome the static pressure and flow out of the drain line Before pu...

Страница 17: ...he Condensing Unit turns on and off based on suction pressure as follows The Evaporator includes a factory installed liquid line solenoid valve LLSV which is controlled by the Evaporator temperature c...

Страница 18: ...18 V3 15 22 Wiring Diagram...

Страница 19: ...QuickConnect Line Set has sufficient length to interconnect the two units If the line set is not long enough do not proceed Contact CellarPro for immediate assistance 2 Reference the Evaporator Mount...

Страница 20: ...tion line connection to the male connection STOP AND MAKE SURE YOU ARE ATTACHING BLUE TO BLUE Hand thread at first to get the threads started without cross threading Once it is too hard to turn by han...

Страница 21: ...d wrap around the coupling provided that the seam is sealed tight Insulating the suction connection is essential to avoid condensation issues 8 Identify the Liquid line marked RED on the female connec...

Страница 22: ...nnections only It is important to keep the drain line level or below the point where it exits the evaporator as it passes through the cutout 11 3000Sqc EC 4000Sqc EC systems rear connections only Appl...

Страница 23: ...o the wall cutout and drywall trim around the connections as desired For serviceability do not use spray foam to insulate around the metal QuickConnect fittings 16 Route the drain line installing a tr...

Страница 24: ...onnection STOP AND MAKE SURE YOU ARE ATTACHING BLUE TO BLUE Follow the previous process to tighten the connection 22 Identify the Liquid line marked RED on the female connector 23 Identify the male Li...

Страница 25: ...nsing unit fans to confirm airflow There shouldn t be any excessive vibration noise or obstructions to airflow Do not leave the system unattended until it has reached normal operating conditions and t...

Страница 26: ...wine which tend to be much colder than storage temperatures especially serving temperatures for white and sparkling wines CellarPro cooling units must be used stored moved and or shipped in the uprigh...

Страница 27: ...ontroller is described in detail in the following section 2 Fan Speed Selector Switch Low Med High The cooling unit fans operate on 3 speed settings Low Medium and High For optimum sound and energy ef...

Страница 28: ...grill of the cooling unit Power On Off Press Power On Off to turn the unit on and off When the Compressor On indicator light is on the Compressor is running When the Fan On indicator light is on the F...

Страница 29: ...Differential of 4 F This means that the cooling unit will turn on when the display rises above 62 F 58 F 4 F and turn off when the display falls below 58 F In this example the average temperature ins...

Страница 30: ...re Differential is unchanged Quick Chill Button To activate the Quick Chill mode press the Up Quick Chill button for three seconds To deactivate Quick Chill press Quick Chill button for three seconds...

Страница 31: ...To activate the Quick Chill mode press the Up button for 3 seconds To deactivate Quick Chill press the Up button for 3 seconds again The Quick Chill indicator Row 3 light will turn on when the cooling...

Страница 32: ...ry preset ENERGY SAVINGS MODE DIFFERENTIAL The factory preset for this setting is 4 This setting controls the Temperature Differential for the Energy Savings Mode The recommended range for this settin...

Страница 33: ...lter is clean 3 Increase the supply of cool air to the space outside the condenser coils using a fan ducting or an exhaust system to remove heat from the space 4 Raise the Minimum Set Point on the coo...

Страница 34: ...eck for loose wires and reconnect Low pressure switch is open On Valve control systems make sure solenoid is energized Jumper out switch to check for a faulty switch and replace if necessary Note that...

Страница 35: ...re power Power supply to fan interrupted loose wire Inspect for loose fan wiring and reconnect Fan capacitor check for loose wires or out of spec capacitance Reconnect loose wires or replace capacitor...

Страница 36: ...op section Condensing unit never shuts off System is wired incorrectly Locate correct wiring diagram for Electronic or Valve controlled system trace wiring and correct If a Valve control system the lo...

Страница 37: ...first 23 hours of operation after the cooling unit is plugged in and or turned on The control panel also will flash a code for each alarm as follows Alarm What it means What to do P1 Probe 1 which sen...

Страница 38: ...ted warranty applies only to cooling units purchased from the factory or an authorized dealer Damage caused by others or by any cause beyond the control of CellarPro shall not be considered defects in...

Отзывы: