Module alarms
Text
ID
Name
Level
Def.
Map
Description
102
Power disturbed
Minor
Transient power alarm with output stopped (module KO)
103
Param phase
query
Minor
No assigned AC group or DC group yet (in progress)
104
Param mismatch
Minor
Param not compatible with the rest of the system
105
No source
Minor
No AC/DC input
106
Vcap too high
Minor
Internal voltage too high
107
Vcap too low
Minor
Internal voltage too low
108
Vref error
Minor
Reference voltage from auxiliary supply out of acceptable
range
109
Memory eeprom
error
Minor
Not implemented
110
Memory flash
error
Minor
Flash continuous verification failed
111
OFF remote
Minor
Module remote OFF
112
OFF manual
Minor
Module OFF manually (ON / OFF switch)
113
BUS com fail
Minor
Too many missing bus frames
114
Bus A fail
Minor
Sync tops reception issue on bus A (com lost)
115
Bus B fail
Minor
Sync tops reception issue on bus B (com lost)
116
Bus sync filter
error
Minor
Sync top filtering circuit fault (detected because sync tops
are received at different times)
117
118
119
Bus A not present Minor
bus A present signal of backplane not seen by the module
120
Bus B not
present
Minor
bus B present signal of backplane not seen by the module
121
Bus frame
collision
Minor
Bus A and bus B are not identical in content
122
Bus fail
Minor
Module can’t see what it writes on both bus
123
Warm up too
high
Minor
One of the measured temperature is above a threshold
124
Power noise
Minor
Transient power alarm (some trips happening)
125
Not defined 30
126
Not defined 31
127
Not defined 32
63
– Flexa 200 - 400/400 – User Manual – v1.0
Содержание FLEXA 200 400/400