![CE+T Power FLEXA 200 400/400 Скачать руководство пользователя страница 62](http://html1.mh-extra.com/html/ce-t-power/flexa-200-400-400/flexa-200-400-400_user-manual_2577174062.webp)
Mappable Events (Not alarms !!)
Text
ID
Name
Level
Def. Map
Description
658
AC out 1 saturated
/
Minor
System load is above the settable limit
(normally 80%)
661
Battery 1 overvoltage
/
Event
662
Battery 2 overvoltage
/
Event
663
Battery 1 overtemperature
/
Event
664
Battery 2 overtemperature
/
Event
665
Battery 1 test active
/
Event
666
Battery 2 test active
/
Event
667
Battery 1 boost active
/
Event
668
Battery 2 boost active
/
Event
722
Battery test cancelled
/
Minor
Battery test has not started because of
another event (See 530 -> 535)
723
SBP failure
/
Major
724
SBP engaged
/
Major
736
AC out 2 failure
/
Major
737
AC out 2 overload
/
Major
738
AC out 2 redundancy lost
/
Event
739
AC out 2 redu1 lost
/
Event
740
AC out 2 saturated
/
Minor
745
AC out 1 manual off
/
Event
746
AC out 2 manual off
/
Event
747
Log full
/
Minor
758
MBP procedure
/
Major + R5
759
Battery safe charging control
/
Major
4.1.1 Module alarms (T4S)
Module alarms
Text
ID
Name
Level
Def.
Map
Description
96
Start
Minor
System is starting
97
Boost not
available
Minor
ACin and ACout not synchronized (boost cannot be used)
98
Boost recovery
Minor
Boost (triac) cooling down from previous activation
99
Boost failure
Minor
Boost (triac) fault short-circuit
100
Fan to be
replaced
Minor
The timeout indicating FAN operates for 7 years
101
Fan failure
Minor
Fans are not functionning properly
62
– Flexa 200 - 400/400 – User Manual – v1.0
Содержание FLEXA 200 400/400
Страница 17: ...17 Flexa 200 400 400 User Manual v1 0 Hardware setup Page 2...