10. SNMP V1 & SNMP V3 Configuration
SNMP is now available on T4S supervisor and on Catena display.
SNMPv1 is available on T4S supervisor. The MIB implemented on T4S SNMP agent is the standard USP MIB defined by
RFC1628.
Catena display now includes a SNMPv1 to SNMPv3 proxy.
The main difference between SNMPv1 and SNMPv3 is the addition of secured connection in SNMPv3.
10.1 SNMPv1 configuration
For SNMPv1 agent configuration, go to Parameters > Monitoring > Network.
See T4S network section for ETH port configuration:
•
IP address.
•
Subnet mask.
•
Gateway.
See T4S SNMP section for SNMP agent configuration:
•
Trap receivers IP addresses. Up to 5 trap receivers can be configured.
•
Note that ports 161 and 162 (for traps) are used. Not configurable.
10.2 SNMPv1 MIB (RFC1628)
The MIB is the standard UPS MIB defined by RFC1628.
Meaning of “input lines”: input lines are AC input groups as existing in T4S web interface. One tri-phase system will
have 3 input lines, one for each phase.
Meaning of “output lines”: output lines are AC output groups as existing in T4S web interface.
The following features of UPS MIB are not implemented in T4S:
•
Writable entries. The current MIB is read-only. Entries can only be edited through the web server. For this reason,
the upsConfig section is also read-only.
•
Bypass values. As T4S doesn’t include the monitoring of bypass devices, bypass measurements are not available
in the MIB. It is however possible to know when the system switched to MBP by reading ups Output Source
value (OID .1.3.6.1.2.1.33.1.4.1).
•
Well known test. Only standard battery test is available. No other test is implemented in T4S at current state.
Any feature defined in RFC1628 that is not in the previous list is available.
10.3 SNMPv3 configuration
For SNMPv3, you need a Catena display. The Catena display can be used as SNMPv1 to SNMPv3 proxy.
The configuration of Catena display is managed by T4S supervisor.
In T4S web interface, go to Parameters > Monitoring > Network.