11.2 Configuration
ModBus slave configuration is accessible through user interface by browsing menu
Parameters, Monitoring Tab,
ModBus submenu.
•
Modbus RTU slave can be either
enabled or disabled.
•
Slave address ranges from
1 to 247. Default is 1.
•
Supported baud rates are:
9600, 19200, 38400, 115200, or 460800. Default is 19200.
•
Parity can be
none, even, or odd. Default is even.
•
Stop bits can be
1 or 2. Default is 1.
•
Configuration is applied once
save button is clicked.
Table version parameters ensure that customer can use any revision of the modbus tables he wants. First release is
based on table revision 1.
11.3 Tables
Data are organized in tables which are described in another document called T4S_Flexa_ModBus_Tables.pdf
47
– Flexa 200 - 400/400 – User Manual – v1.0