ATRIUM A22POE

2-Door Controller

  INSTALLATION MANUAL

EN

ATRIUM A22POE

2-Door Controller

  INSTALLATION MANUAL

DOOR LOCk DEVICES

Each controller has two lock outputs. The LOCK OUTPUT can be configured to provide power (750mA @ 12Vdc), 

see “Jumper Settings” on this page, the LOCK OUTPUT is protected by a fuseless protection algorithm and will 

shutdown if the current exceeds 750mA @ 12Vdc. When a different voltage or more current is required, we 

recommend to use the RELAY OUTPUT configuration (see “Wiring Diagram of Locking Device”, page 22).

• If you have one door with a reader on each side of the door, you can use either lock output.
• You can program the lock outputs to function in “fail-safe” (remove power to unlock a door) or

  “fail-secure” mode (power required to unlock a door).

• When using electromagnetic door locks or similar devices ensure that the current specifications are 

not exceeded.

Always consult the regulatory agency in your area for existing regulations regarding doors designated 

as emergency exits.

Jumper Settings

The jumpers LOCK1 and LOCK2 must be set according to the door devices used (see “Wiring Diagram of 

Locking Device”, page 22).
If the lock (or electromagnetic) requires 24Vdc, you m  ia gram”, page 22. The same applies if the Locking 

Device requires an alternating current supply (Vac).

INPUTS/
OUTPUTS

RS485
LOCAL
BUS

BATTERY

(12V DC)

INPUT

POWER

SUPPLY

ETHERNET

LOCAL

BUS

STATUS

LOCK 1

SETTING

LOCK 2

SETTING

READERS

INPUTS

LOCKS

A22

2-Door Web-Based IP Module

DOOR 1

DOOR 1

DOOR 2

DOOR 2

DOOR 1

DOOR 2

D

ATA

 1

Red LED 1

Green LED 1

Buzzer 1

D

ATA

 0

+12V DC

D

ATA

 1

Red LED 2

Green LED 2

Buzzer 2

D

ATA

 0

+12V DC

Com. Relay 1

N.O. Relay 1

N.C. Relay 1

Lock output 1

Com. Relay 2

N.O. Relay 2

N.C. Relay 2

Lock output 2

Door Contact 1

REX 1

+12V DC

Door Contact 2

REX 2

+12V DC

Tamper Switch

+24V DC

-

+12V DC

-

+12V DC

A+

B-

Input 1

Input 2

Output 1

+12 V DC

Output 2

ETHERNET

24V DC INPUT

BATTERY

MODULE TYPE

SYSTEM STATUS

Electromagnetic Door Lock

(Door 2)

Door Strike

(Door 1)

+

-

+

-

Lock Output Jumper Settings

There are two jumpers, one for each lock output, LK1 and LK2. 

Each output provides 750mA at 12VDC

Default setting:

The lock output will be at 0Vdc in

normal state and toggles to

12Vdc during the unlock time.

(De-energize lock output)

The lock output will be at 12Vdc in 

normal state and toggles to 0Vdc during 

the unlock time. This is the typical

setting for electromagnetic door lock.

(Energize lock output)

Jumper Side View

or

Jumper Side View

12V

0V

12V

0V

Содержание ATRIUM A22POE

Страница 1: ...The installer s choice cdvigroup com ENGLISH EN A22POE Web Based PoE 2 Door Hybrid Controller Power Over Ethernet...

Страница 2: ...N 3 2 NOTES AND RECOMMENDATIONS 4 FCC IC Compliance 4 UL Compliance 4 UL 294 Compliance Notice 4 Free Technical Support 4 Recommended Wiring 5 Specifications 5 3 PACKAGE CONTENTS 7 Location and Mounti...

Страница 3: ...t an industry leader in efficiency and simplicity Control 2 doors 2 readers Embedded Web Server Pre assembled PoE Splitter On board Ethernet Port with AES 256 bit encryption Auto detect hardware modul...

Страница 4: ...eaders Wiegand 26 bit 30 bit and 40 bit mag stripe up to 32 digits Use of a UL recognized tamper switch on every housing cabinet for the A22POE Use only UL listed cables Use only UL listed adaptors No...

Страница 5: ...pandable to 10 doors Cards and users Up to 10 000 cards and users Schedules Up to 250 Schedules each supporting up to 100 time periods dd hh mm Buffered Events Up to 25 000 events Holidays Up to 100 h...

Страница 6: ...nt limited monitored Power output specifications Battery Backup Battery Capacity 12Vdc 7Ah rechargeable acid lead or gel cell backup battery UL ULC YUASA NP7 12 recommended Europe CDVI B7AH recommende...

Страница 7: ...d a white wire 115mm 3 wires for tamper switch 2 x 360mm and 1 x 165mm Bolts and Nuts Wall Switch Spacer Door Switch and 2 white wires 350mm Door Switch Support Metal box screw for door enclosure Meta...

Страница 8: ...et Can Accommodate One 12Vdc 4 5AH or 7AH gel cell type batteries and wiring connections 15cm 6 high 6cm 2 5 wide 9 cm 3 54 deep Battery Model Voltage Capacity Length Width Height YUASA NP7 12 12 Volt...

Страница 9: ...be prepared before fixing it to its location Installing the Tamper Switches Installing tamper switches allows the A22POE to detect when the cabinet door is opened and or when the cabinet is removed f...

Страница 10: ...abinet Side View Cabinet Door Nut Spacer Spacer Screw Spacer Install the wall tamper switch using the supplied bolts and nuts as shown in the following picture Install the tamper switch plastic spacer...

Страница 11: ...bracket on the mounting flange Door Tamper Switch Bracket Door Tamper Switch Mounting Flange Install the door tamper switch by aligning the switch holes to the pre installed plastic bracket pins Press...

Страница 12: ...he box door knock out 2 Insert the lock in the hole 3 Slide the U metal part into the lock groove to secure the lock in place Alternatively or complementary to the box lock the box may be secured by f...

Страница 13: ...ing the Box to its Location Install the box to its location using 4 screws not supplied as shown in the following picture If the wall tamper switch is used make sure that the tamper switch arm moves f...

Страница 14: ...nstalling the A22POE PC board Install the 5 fasteners PCB holder supplied respectively to the box holes identified in red in the following picture Install the A22POE PCB by aligning the fasteners with...

Страница 15: ...PUTS RS485 LOCAL BUS BATTERY 12V DC INPUT POWER SUPPLY ETHERNET LOCAL BUS STATUS LOCK 1 SETTING LOCK 2 SETTING READERS INPUTS LOCKS A22 2 Door Web Based IP Module DOOR 1 DOOR 1 DOOR 2 DOOR 2 DOOR 1 DO...

Страница 16: ...ch to the TMP terminals using the supplied wire 2 Connect the other terminal of the same tamper switch to the GND terminals using the supplied wire If you do not use the tamper switch connect a wire b...

Страница 17: ...has been left open after a valid access or the door has been forced open The functions of all these outputs are programmable through the ATRIUM software INPUTS OUTPUTS RS485 LOCAL BUS BATTERY 12V DC...

Страница 18: ...fferentiate between a door forced open and an authorized exit Inputs REX 1 and REX 2 are assigned by default for Door 1 and Door 2 REX inputs respectively Door 1 Factory Default Input Settings same se...

Страница 19: ...r INPUT in Software as described in the following figure This setup will not support WIRE CUT supervision but offers WIRE SHORT supervision and will generate an alarm condition when the state of the i...

Страница 20: ...will support WIRE CUT supervision but not WIRE SHORT supervision and will generate an alarm condition when the state of one of the input is breached WIRE SHORT supervision NO WIRE CUT supervision YES...

Страница 21: ...of Locking Device page 22 If the lock or electromagnetic requires 24Vdc you m ia gram page 22 The same applies if the Locking Device requires an alternating current supply Vac INPUTS OUTPUTS RS485 LOC...

Страница 22: ...Output 2 ETHERNET 24V DC INPUT BATTERY MODULE TYPE SYSTEM STATUS Electromagnetic Door Lock Door 2 Door Strike Door 1 De energize lock output Energize lock output 12V 0V 12V 0V ETHERNET LOCAL BUS STAT...

Страница 23: ...mmable Adaptive battery charging algorithm 250mA default 320mA 500mA or 1A Intelligent battery monitoring charging algorithms allowing optimum performance using standard lead acid or gel cell type bat...

Страница 24: ...can be used The battery charge current can be set to either 250mA default 320mA 500mA or 1A Refer to the ATRIUM user interface instruction manual for more information on how to modify the battery char...

Страница 25: ...24V DC INPUT BATTERY MODULE TYPE SYSTEM STATUS 1 5 6 2 3 4 1 ETHERNET ACT Green LED flashing Data transmitted received LNK Green LED Ethernet network detected 2 LOCAL BUS RX Green LED flashing Data r...

Страница 26: ...DOOR 1 DOOR 2 DOOR 2 DOOR 1 DOOR 2 DATA 1 Red LED 1 Green LED 1 Buzzer 1 DATA 0 12V DC DATA 1 Red LED 2 Green LED 2 Buzzer 2 DATA 0 12V DC Com Relay 1 N O Relay 1 N C Relay 1 Lock output 1 Com Relay 2...

Страница 27: ...ller or expander on page 15 to set an A22POE as an expander Connect the expander modules using these topologies cdvigroup com cdvigroup com cdvigroup com cdvigroup com cdvigroup com A22POE A22POE A22P...

Страница 28: ...begin flashing in sequence 2 Red flashes 2 Green Enrollment mode is active 3 Present cards one by one to the reader NEW cards will be ADDED Green LED will flash and a quick beep will be emitted Each n...

Страница 29: ...ble in the event of loss or non presentation of the form The 5 Year Warranty only applies to products installed by a skilled and experienced personal with the necessary trade qualifications to install...

Страница 30: ...consumables such as fuses lights and batteries for example Failure or malfunctioning as a result of an accident poor storage conditions unsuitable assembly bad utilization or handling poor maintenanc...

Страница 31: ...31 cdvigroup com EN ATRIUM A22POE 2 Door Controller INSTALLATION MANUAL NOTES...

Страница 32: ...ANADA USA LATIN AMERICA Phone 1 450 682 7945 Fax 1 450 682 9590 CDVI BENELUX BELGIUM NETHERLAND LUXEMBOURG Phone 32 0 56 73 93 00 Fax 32 0 56 73 93 05 CDVI TAIWAN Phone 886 0 42471 2188 Fax 886 0 4247...

Отзывы: