READERS AND KEyPADS

The A22POE allows automatic format detection and decoding of the connected reader/keypad. When installing 

a keypad with a Wiegand output, the keypad’s “D0” and “D1” wires should be connected to the same terminals 

as the reader (the reader or keypad LED and buzzer outputs must be open collector).

The ATRIUM system is configured by default for the NANO, STAR and SOLAR reader models which display 

a bright blue backlight in standby mode. A list of other CDVI readers and keypads is shown below. Other 

popular wiegand readers and keypads are also supported. Contact us to confirm compatibility. Most readers 

and keypads have built-in buzzers and LEDs. These should be connected to module’s programmable outputs 

(B1, G1, R1 for READER 1 and B2, G2, R2 for READER 2). These are open collector outputs capable of sinking 

100mA. Please note that the B, G and R outputs are programmed for a 7-wire reader by default. Typically, a 

blue/red/green indicator on the reader will inform the card user that access has been granted (changes from 

blue to green), access has been denied (changes from blue to flashing red), door is locked (from blue to brief 

red) or door is unlocked by a schedule (changes from blue to brief green). Typically, the reader buzzer or an 

external sounding device will inform the card user that the door has been left open after a valid access or the 

door has been forced open. The functions of all these outputs are programmable through the ATRIUM software.

INPUTS/
OUTPUTS

RS485
LOCAL
BUS

BATTERY

(12V DC)

INPUT

POWER

SUPPLY

ETHERNET

LOCAL

BUS

STATUS

LOCK 1

SETTING

LOCK 2

SETTING

READERS

INPUTS

LOCKS

A22

2-Door Web-Based IP Module

DOOR 1

DOOR 1

DOOR 2

DOOR 2

DOOR 1

DOOR 2

D

ATA

 1

Red LED 1

Green LED 1

Buzzer 1

D

ATA

 0

+12V DC

D

ATA

 1

Red LED 2

Green LED 2

Buzzer 2

D

ATA

 0

+12V DC

Com. Relay 1

N.O. Relay 1

N.C. Relay 1

Lock output 1

Com. Relay 2

N.O. Relay 2

N.C. Relay 2

Lock output 2

Door Contact 1

REX 1

+12V DC

Door Contact 2

REX 2

+12V DC

Tamper Switch

+24V DC

-

+12V DC

-

+12V DC

A+

B-

Input 1

Input 2

Output 1

+12 V DC

Output 2

ETHERNET

24V DC INPUT

BATTERY

MODULE TYPE

SYSTEM STATUS

GALEO/W

Wiegand Keypad

NANOPB

Mini Proximity Reader

Red

Black

Green

White

Orange

Yellow

Brown

Red

Black

Green

White

Brown

See chapter 2 “Recommended Wiring” for more information on wiring type, size, and maximum length.
Compatible readers and keypads:

•NANOPW (White) and NANOPB (Black)
•STARPW (White) and STARPB (Black)
•SOLARPW (White) and SOLARPB (Black)
•DGLP FN WLC26

•DGLP WLC26
•DGLI F WLC26
•DGLI WLC26
•DGLP60WLC

•KCPROXWLC (Reader & Keypad)
•DGLM (Magstripe)

And most popular Wiegand
readers & keypad

For an up-to-date list of which keypads and readers are supported, refer to the ATRIUM Software 

Manual or visit our web site at www.cdvigroup.com.

Please note that the A22POE provides 12Vdc output. Connecting a device (keypad or reader) requiring 

a different voltage may damage the reader or keypad and invalidate the A22POE warranty.

Содержание ATRIUM A22POE

Страница 1: ...The installer s choice cdvigroup com ENGLISH EN A22POE Web Based PoE 2 Door Hybrid Controller Power Over Ethernet...

Страница 2: ...N 3 2 NOTES AND RECOMMENDATIONS 4 FCC IC Compliance 4 UL Compliance 4 UL 294 Compliance Notice 4 Free Technical Support 4 Recommended Wiring 5 Specifications 5 3 PACKAGE CONTENTS 7 Location and Mounti...

Страница 3: ...t an industry leader in efficiency and simplicity Control 2 doors 2 readers Embedded Web Server Pre assembled PoE Splitter On board Ethernet Port with AES 256 bit encryption Auto detect hardware modul...

Страница 4: ...eaders Wiegand 26 bit 30 bit and 40 bit mag stripe up to 32 digits Use of a UL recognized tamper switch on every housing cabinet for the A22POE Use only UL listed cables Use only UL listed adaptors No...

Страница 5: ...pandable to 10 doors Cards and users Up to 10 000 cards and users Schedules Up to 250 Schedules each supporting up to 100 time periods dd hh mm Buffered Events Up to 25 000 events Holidays Up to 100 h...

Страница 6: ...nt limited monitored Power output specifications Battery Backup Battery Capacity 12Vdc 7Ah rechargeable acid lead or gel cell backup battery UL ULC YUASA NP7 12 recommended Europe CDVI B7AH recommende...

Страница 7: ...d a white wire 115mm 3 wires for tamper switch 2 x 360mm and 1 x 165mm Bolts and Nuts Wall Switch Spacer Door Switch and 2 white wires 350mm Door Switch Support Metal box screw for door enclosure Meta...

Страница 8: ...et Can Accommodate One 12Vdc 4 5AH or 7AH gel cell type batteries and wiring connections 15cm 6 high 6cm 2 5 wide 9 cm 3 54 deep Battery Model Voltage Capacity Length Width Height YUASA NP7 12 12 Volt...

Страница 9: ...be prepared before fixing it to its location Installing the Tamper Switches Installing tamper switches allows the A22POE to detect when the cabinet door is opened and or when the cabinet is removed f...

Страница 10: ...abinet Side View Cabinet Door Nut Spacer Spacer Screw Spacer Install the wall tamper switch using the supplied bolts and nuts as shown in the following picture Install the tamper switch plastic spacer...

Страница 11: ...bracket on the mounting flange Door Tamper Switch Bracket Door Tamper Switch Mounting Flange Install the door tamper switch by aligning the switch holes to the pre installed plastic bracket pins Press...

Страница 12: ...he box door knock out 2 Insert the lock in the hole 3 Slide the U metal part into the lock groove to secure the lock in place Alternatively or complementary to the box lock the box may be secured by f...

Страница 13: ...ing the Box to its Location Install the box to its location using 4 screws not supplied as shown in the following picture If the wall tamper switch is used make sure that the tamper switch arm moves f...

Страница 14: ...nstalling the A22POE PC board Install the 5 fasteners PCB holder supplied respectively to the box holes identified in red in the following picture Install the A22POE PCB by aligning the fasteners with...

Страница 15: ...PUTS RS485 LOCAL BUS BATTERY 12V DC INPUT POWER SUPPLY ETHERNET LOCAL BUS STATUS LOCK 1 SETTING LOCK 2 SETTING READERS INPUTS LOCKS A22 2 Door Web Based IP Module DOOR 1 DOOR 1 DOOR 2 DOOR 2 DOOR 1 DO...

Страница 16: ...ch to the TMP terminals using the supplied wire 2 Connect the other terminal of the same tamper switch to the GND terminals using the supplied wire If you do not use the tamper switch connect a wire b...

Страница 17: ...has been left open after a valid access or the door has been forced open The functions of all these outputs are programmable through the ATRIUM software INPUTS OUTPUTS RS485 LOCAL BUS BATTERY 12V DC...

Страница 18: ...fferentiate between a door forced open and an authorized exit Inputs REX 1 and REX 2 are assigned by default for Door 1 and Door 2 REX inputs respectively Door 1 Factory Default Input Settings same se...

Страница 19: ...r INPUT in Software as described in the following figure This setup will not support WIRE CUT supervision but offers WIRE SHORT supervision and will generate an alarm condition when the state of the i...

Страница 20: ...will support WIRE CUT supervision but not WIRE SHORT supervision and will generate an alarm condition when the state of one of the input is breached WIRE SHORT supervision NO WIRE CUT supervision YES...

Страница 21: ...of Locking Device page 22 If the lock or electromagnetic requires 24Vdc you m ia gram page 22 The same applies if the Locking Device requires an alternating current supply Vac INPUTS OUTPUTS RS485 LOC...

Страница 22: ...Output 2 ETHERNET 24V DC INPUT BATTERY MODULE TYPE SYSTEM STATUS Electromagnetic Door Lock Door 2 Door Strike Door 1 De energize lock output Energize lock output 12V 0V 12V 0V ETHERNET LOCAL BUS STAT...

Страница 23: ...mmable Adaptive battery charging algorithm 250mA default 320mA 500mA or 1A Intelligent battery monitoring charging algorithms allowing optimum performance using standard lead acid or gel cell type bat...

Страница 24: ...can be used The battery charge current can be set to either 250mA default 320mA 500mA or 1A Refer to the ATRIUM user interface instruction manual for more information on how to modify the battery char...

Страница 25: ...24V DC INPUT BATTERY MODULE TYPE SYSTEM STATUS 1 5 6 2 3 4 1 ETHERNET ACT Green LED flashing Data transmitted received LNK Green LED Ethernet network detected 2 LOCAL BUS RX Green LED flashing Data r...

Страница 26: ...DOOR 1 DOOR 2 DOOR 2 DOOR 1 DOOR 2 DATA 1 Red LED 1 Green LED 1 Buzzer 1 DATA 0 12V DC DATA 1 Red LED 2 Green LED 2 Buzzer 2 DATA 0 12V DC Com Relay 1 N O Relay 1 N C Relay 1 Lock output 1 Com Relay 2...

Страница 27: ...ller or expander on page 15 to set an A22POE as an expander Connect the expander modules using these topologies cdvigroup com cdvigroup com cdvigroup com cdvigroup com cdvigroup com A22POE A22POE A22P...

Страница 28: ...begin flashing in sequence 2 Red flashes 2 Green Enrollment mode is active 3 Present cards one by one to the reader NEW cards will be ADDED Green LED will flash and a quick beep will be emitted Each n...

Страница 29: ...ble in the event of loss or non presentation of the form The 5 Year Warranty only applies to products installed by a skilled and experienced personal with the necessary trade qualifications to install...

Страница 30: ...consumables such as fuses lights and batteries for example Failure or malfunctioning as a result of an accident poor storage conditions unsuitable assembly bad utilization or handling poor maintenanc...

Страница 31: ...31 cdvigroup com EN ATRIUM A22POE 2 Door Controller INSTALLATION MANUAL NOTES...

Страница 32: ...ANADA USA LATIN AMERICA Phone 1 450 682 7945 Fax 1 450 682 9590 CDVI BENELUX BELGIUM NETHERLAND LUXEMBOURG Phone 32 0 56 73 93 00 Fax 32 0 56 73 93 05 CDVI TAIWAN Phone 886 0 42471 2188 Fax 886 0 4247...

Отзывы: