Single with WIRE SHORT and WIRE CUT Supervision
(Limit of 1 Detection Device on the Input)
When using this method, only one device can be connected to
the input. The input must be connected using only one Contact (NO
or NC: programmable per INPUT in Software) as described in the
following figure. This setup will support both WIRE CUT and WIRE SHORT
supervision and will generate an alarm condition when the state of the
input is breached.
WIRE SHORT supervision: YES (Detected as INPUT SHORT)
WIRE CUT supervision: YES (Detected as INPUT CUT)
Doubled with WIRE CUT Supervision
(2 Detection Device on the Input)
When using this method, two device
can be connected to the input. The input must
be connected using two Contacts (NO or NC:
programmable per INPUT in Software) as
described in the following figure. This setup
will support WIRE CUT supervision but not
WIRE SHORT supervision and will generate an
alarm condition when the state of one of the
input is breached.
WIRE SHORT supervision: NO
WIRE CUT supervision: YES (Detected as INPUTS CUT)
Doubled with WIRE SHORT and WIRE CUT Supervision
(2 Detection Device on the Input)
When using this method, two device can be connected to the
input. The input must be connected using two Contacts (NO or NC:
programmable per INPUT in Software) as
described in the following figure. This setup
will support WIRE CUT and WIRE SHORT
supervision and will generate an alarm
condition when the state of one of the input is
breached.
WIRE SHORT supervision: YES
(Detected as INPUTS SHORT)
WIRE CUT supervision: YES
(Detected as INPUTS CUT)
1K
EOL
1K
Tamper Input 1
Input 1
12V Z1 GND Z2 Z3 GND Z4 Z5
INPUTS
1K
2.2K
Tamper Input 1
Tamper Input 11
Input 1
Input 11
12V Z1 GND Z2 Z3 GND Z4 Z5
INPUTS
Detection device #1
Detection device #2
1K
1K
EOL
2.2K
Tamper Input 1
Tamper Input 11
Input 1
Input 11
12V Z1 GND Z2 Z3 GND Z4 Z5
INPUTS
Detection device #1
Detection device #2