CD Automation srl
STE Soft Starter
User’s Manual
29
6.3
Analog Inputs
The STE Soft Starter has 2 analog inputs:
The Analogue Input 1 is configurable (0÷10V, 4÷20mA, ecc), and the Analogue Input 2 is for the PTC
probe.
6.3.1
Analogue Input 1 (Terminals 8 and 7) OPTION
The Analogue Input 1 is used with the option Control to set voltage at the end of start.
The Analogue Input 1 for default is already configured for 0÷10Vdc input signal, however if you wish to
change the Analogue Input 1 (ex. from 0÷10V to 4÷20mA) proceed as follows:
Caution:
this procedure must be performed only by qualified persons
Control board Size 9
Control board Size 11/13/14
JP6
Type Input
features
Jumper
0
÷
10V (default)
Impedance 40K
Ω
Open
POT Impedance
10K
Ω
min
Open
4
÷
20mA
Impedance 500
Ω
Close
JP8