CD Automation srl
STE Soft Starter
User’s Manual
45
P023 (H17)
1,/
Kickstart Value (Initial Boost)
%
R/W
Function:
This parameter set the Kickstart value in % of full voltage.
This function provides extra torque at the beginning of a start. This can be
useful for accelerating high friction loads that require high breakaway torque
but then accelerate easily
Min/Max:
0.0 ÷ 80.0%
Default: 0.0
(Off)
Example:
Note:
Ensure the motor can handle this extra torque before applying this function
P024 (H18)
1:.
Kickstart Time
msec
R/W
Function:
This parameter set the time of initial boost when the Kickstart function is
active.
Min/Max:
0 ÷ 20 (10msec ogni step)
Default: 10
(=100msec)
P032 (H20)
*@:=
Deceleration Ramp
Sec
R/W
Function:
This parameter set the time for motor deceleration.
Min/Max:
0 ÷ 60 seconds
Default: 10
Note:
used only with Deceleration Ramp stop mode
P033 (H21)
-)/@
Stop Type
R/W
Function:
This parameter selects the motor Stop Type.
Value:
0= Freewheel stop mode
1= Deceleration Ramp stop mode
Default: 0
P038 (H26)
)/:
Motor PTC Probe Function
R/W
Function:
This parameter set the Motor PTC Probe as the critical alarm
Value:
0 = Motor PTC Probe not Critical Alarm
1 = Motor PTC Probe Critical Alarm
Default: 0
P040 (H28)
0C'
Unbalance Threshold
%
R/W
Function:
This parameter set in % the maximum admissible value for the phases
unbalance protection
Min/Max:
0 ÷ 100.0%
Default: 50.0