User’s Manual
46
P041 (H29)
0C/
Unbalance Alarm Delay
Sec
R/W
Function:
This parameter set the time for delay the unbalance protection.
Min/Max:
0 ÷ 100 seconds
Default: 20
P044 (H2C)
00:'
Undervoltage Threshold
%
R/W
Function:
This parameter contains Threshold voltage value, set in % of Voltage supply,
for the Undervoltage protection.
Min/Max:
0 ÷ 100.0%
Default: 75.0
P045 (H2D)
00:/
Undervoltage Alarm Delay
Sec
R/W
Function:
This parameter set the time for delay the Undervoltage protection
Min/Max:
0 ÷ 10,0 seconds
Default: 1,0
P046 (H2e)
0:$
Overvoltage Threshold
%
R/W
Function:
This parameter contains Threshold voltage value, set in % of Voltage supply,
for the Overvoltage protection.
Min/Max:
125.0 ÷ 150.0%
Default: 125.0
P047 (H2F)
0:/
Overvoltage Alarm Delay
Sec
R/W
Function:
This parameter set the time for delay the Overvoltage protection.
Min/Max:
0 ÷ 10,0 seconds
Default: 1,0
P072 (H48)
/$'
Thermal Overload Threshold
%
R/W
Function:
This parameter contains Threshold current value, set in % of nominal motor
current (FL_A), for the Thermal Overload protection.
Under this value the Thermal Overload protection doesn’t work.
Min/Max:
80 ÷ 150%
Default: 110
P074 (H4A)
/$/)
Thermal Overload type
%
R/W
Function:
This parameter set the type of Motor thermal curve
Value:
0= class 2 (Light Curve)
1= class 10A (for standard application)
2= class 20 (for severe application)
3= class 30 (Heavy Curve)
Default: 1