CD Automation srl
STE Soft Starter
User’s Manual
31
6.4
Analog Outputs
The STE Soft Starter has 1 configurable analog output (0÷10V, 4÷20mA, ecc). The analog output is for
retransmitting the average power or for the average current of all phases(default). (see par. 9)
6.4.1
Analogue Output (Terminals 10 and 6 or 10 and 7)
The Analogue Output for default is already configured for 0÷10Vdc output signal, however if you wish to
change the Analogue Output (ex. from 0÷10V to 4÷20mA) proceed as follows:
Caution:
this procedure must be performed only by qualified persons
Control board Size 9
Control board Size 11/13/14
JP2
C B A
Type Output
features
P100
(
Jumper
0
÷
10V (default)
20mA Max
0
A-B
0
÷
20mA 500
Ω
Max
0 B-C
4
÷
20mA 500
Ω
Max
1 B-C
JP21
C B A
Setting the Output Value
The parameter P099
:#
allows to set the full scale value to have the maximum output,
for example if you use an indicator with full scale 50A set the parameter P099
:#
= 50.