12.3
Analog Inputs
The CD3000E thyristor unit has 2 configurable analog inputs (0÷10V, 4÷20mA, ecc):
The primary input for the analog setpoint, the secondary input for the Current Profiler or Ext. Feed-Back.
12.3.1
Primary Input (Terminals 8 and 7)
The primary input is already configured in line with customer requirements that are defined in the Order
Code. The Order Code is written on the identification label.
However, if you wish to change the primary input (ex. from 0÷10V to 4÷20mA) proceed as follows:
Size S09
Size S11/S13/S14
JP6
Type
Input features
Jumper
0
÷
10V (default)
Impedance
40K
Ω
Open
POT
Impedance
10K
Ω
min
Open
4
÷
20mA
Impedance
500
Ω
Close
JP8
Primary Input calibration procedure
When you change the hardware setting is necessary make the Input calibration procedure.
To make the Input calibration procedure follow these steps:
•
Give the power supply.
•
With Control Panel go in the Hardware menu (P000
= 5)
•
Set the input signal to the min value (ex. 0V for 0÷10V or 4mA for 4÷20mA)
•
Set the parameter P057
= 1
•
Press ENTER key
•
Set the input signal to the max value (ex.10V for 0÷10V or 20mA for 4÷20mA)
•
Set the parameter P058
= 1
•
Press ENTER key
The Input calibration procedure is done.