CD Automation srl
CD3000E-3PH from 25A to 500A
User’s Manual
52
14
Configuration Parameters
The Configuration Parameters are accessible from the Control Panel (place in front of unit), from the
software configurator or through the serial communication port RS485.
With the RS485 Serial Port the parameters are not divided by menu, but only by numerical order.
14.1
Operator Menu
P000 (H00)
Password
R/W
Function:
This parameter gives access at the available menus.
Value:
0 = Operator Menu
5 = Setup Menu
10 = Hardware Menu
Note:
With the RS485 Serial Port this parameter are not used.
P001 (H01)
Code of Critical alarm
R
Function:
This parameter read only gives information on the following alarms that they
stop the CD3000E.
Valore:
00 = No Alarm
01 = Phase Loss
20 = External Alarm
40 = Heat-sink over temperature
Note:
If more alarms occur, the value will be equal at the sum of the two alarms.
example: External Alarm + Phase Loss= 20 + 01 = 21
P002 (H02)
Code of Not Critical alarm
R
Function:
This parameter read only gives information on the following alarms that don't
stop the CD3000E.
Value:
00 = No Alarm
01 = Thyristor Failure
02 = Heater Break Alarm
04 = Unbalanced Load
Note:
If more alarms occur, the value will be equal at the sum of the two alarms.
example: Thyristor F Heater Break Alarm = 01 + 02 = 03
P003 (H03)
Setpoint selection Analog / Digital
R/W
Function:
This parameter determines the use of the analog setpoint (terminal 7-8) or of
the digital setpoint setted in the parameter P004
.
Value:
0 = Analog setpoint
1 = Digital setpoint
Default:
0
Note:
The parameter is not memorized in EEPROM.
P004 (H04)
Setpoint Digital Value
%
R/W
Function:
This parameter contains the digital setpoint value, active with
P003
= 1
Min/Max:
0 ÷ 100%
Default:
0
Note:
The parameter is not memorized in EEPROM.
P008 (H08)
Valore Setpoint Analogico
%
R
Function:
This parameter read only contains the analog setpoint value present at the
terminals 7-8 of the command terminals.
Min/Max:
0 ÷ 100%
Example:
With input 4÷20mA:
Input 4mA P008
= 0
Input 12mA P008
= 50
Input 20mA P008
= 100
Содержание CD3000 E-3PH