P112 (H70)
Digital output configuration (terminal 16)
R/W
Function:
This parameter selects the function of the digital output.
Value:
0 = Thyristor Failure
1 = Heater Break Alarm (HB)
2 = Unbalanced Load
3 = Current limit active
Default:
1
P113 (H71)
Digital output configuration (terminal 11 and 12)
R/W
Function:
This parameter selects the function of the digital output.
Value:
0 = Thyristor Failure
1 = Heater Break Alarm (HB)
2 = Unbalanced Load
3 = Low voltage
Default:
0
Note:
Not available for size S09
P114 (H72)
Baud Rate
R/W
Function:
This parameter selects the Baud rate on the serial port.
Value:
0 = 4800
1 = 9600
2 = 19200
Default:
2
P115 (H73)
Address
R/W
Function:
This parameter selects the Address on the serial port for the thyristor unit.
Min/Max:
1 ÷ 127
Default:
1