CD Automation srl
CD3000E-3PH from 25A to 500A
User’s Manual
58
15
Internal Fuse
The CD3000E thyristor unit have internal fuse extrarapid at low I²t for the thyristor protection of against
the short-circuits.
The fuse must have I²t lower than the thyristor one (I²t max)
Caution:
USE
ONLY
EXTRARAPID
FUSE
WITH
APPROPRIATE
I²
T
15.1
Fuse Code
200 kARMS Symmetrical A.I.C.
Size
Fuse CODE
Current
(A RMS)
I²T
(A²sec)
Vac
Qty
25A (S09)
2x50 073 06.100
2 x 100
10540
660
3
35A (S09)
2x50 073 06.100
2 x 100
10540
660
3
45A (S09)
2x50 073 06.100
2 x 100
10540
660
3
75A (S09)
2x50 073 06.100
2 x 100
10540
660
3
100A (S11)
20 282 20.180
180
16320
660
3
125A (S11)
20 282 20.180
180
16320
660
3
150A (S11)
20 282 20.250
250
35200
660
3
225A (S13)
20 559 20.315
315
61600
660
3
300A (S14)
FU450FMM
450
84000
660
3
350A (S14)
FU550FMM
550
193500
660
3
400A (S14)
FU550FMM
550
193500
660
3
450A (S14)
FU700FMM
700
378000
660
3
500A (S14)
FU700FMM
700
378000
660
3
600A (S14)
FU700FMM
700
378000
660
3
Caution:
The Fuses must have I²t 20% less than thyristor's I²t.
Caution:
High speed fuses are used only for the thyristor protection and can not be used to
protect the installation.
Caution:
The warranty of thyristor is null if no proper fuses are used. See tab.
Warning:
The user installation must be protected by electromagnetic circuit breaker or by
fuse isolator.